Board Mountable
DC-DC Converters
IMS 7 Series
Electrical Input Data
General conditions:
– TA = 25°C, unless TC is specified.
– Connector pins i and Vi– interconnected.
– R input not connected.
Table 2: Input Data
Input
24 IMS
48 IMS
Characteristics
Conditions
min
14
typ
max
36
min
36
typ
max
75
Unit
Ui
Input voltage range 1
TA min...TA max
Io = 0...Io nom
V DC
Ui nom
Ui sur
Input voltage (nominal)
24
48
Repetitive surge
voltage
Abs. max input (3 s)
50
100
tstart up
Converter 2
start-up time
switch on
inh. release
Worst case condition at
Ui min and full load
0.25
0.5
0.1
0.25
0.5
0.1
s
trise
Rise time 2
Ui nom, Io = Io nom
resistive load
5
12
5
ms
capacitive load
Io = 0, Ui min...Ui max
for surge calculation
Converter operating
Converter inhibited
Converter operating
Converter inhibited
Ui min...Ui max
12
6
Iio
No load input current
Input capacitance
Inhibit voltage
12
24
12
mA
µF
Ci
Uih
0.8
0.5
–10...0.8
–10 ...0.8
V DC
open, 2.4...Ui max
open, 2.4...Ui max
Iih
Inhibit current
–0.5
–0.5
mA
1
1
Ii ih
Input current
3.0
3.0
if unit inhibited
Iinr p
fs
Peak inrush current 4
Switching frequency
Reflected ripple current
Ui = Ui nom
4.0
3.9
A
Ui min...Ui max, Io = 0...Io nom
Io = 0...Io nom
approx. 330
approx. 330
kHz
mApp
Ii rr
40
30
Ui RFI
Input RFI level
EN 55022 3
B
B
conducted and radiated
1 Ui min will not be as stated if Uo is increased above Uo nom by use of the R input pin. If the output voltage is set to a higher value, Ui min
will be proportionally increased.
2 Measured with a resistive or max. admissible capacitive load. (See fig.: Converter start-up and rise time).
3 Measured with a lead lenght of 0.1 m, leads twisted. Double output units with both outputs in parallel.
4 Source impedance according to prETS 300132-2, version 4.3.
5 The level of the switching frequency band varies with the output voltage configuration. (See also fig.: Switching frequency versus
input voltage and load.)
Uo
trise
04008
Uo nom
t
tstart up
Fig. 5
Converter start-up and rise time
Edition 6/4.2000
4/16