400 Series™
4-Wire Duct
Smoke Detector
A Division of Pittway
3825 Ohio Avenue, St. Charles, IL 60174
1-800-SENSOR2 (736-7672), Fax 630-377-6495
http://www.systemsensor.com
Models Available
DH400ACDCI Ionization Duct Smoke Detector
DH400ACDCA Ionization Detector, ULC Listed
DH400ACDCP Photoelectronic Duct Smoke Detector
Features
• 24 VAC/DC or 120/220 VAC operation
• Simple change-out of photo or ion detector heads
• Air velocity rating from 500 to 4000 FPM
• Powered outputs for remote LED and sounder
• Remote test station option
detector heads allow easy removal for quick cleaning and
maintenance, or a change in application without removing
the duct housing. The DH400ACDC samples air currents
passing through a duct and gives dependable performance
for management of fans, blowers, and air conditioning
systems.
• Remote sounder option
• Equipped with a DPDT auxiliary relay (two Form C
contacts)
WARNING: Duct smoke detectors have specific limitations.
• Easy and quick mounting to round or rectangular ducts
from 1′ – 12′ wide
DUCT DETECTORS ARE:
• Clear cover for convenient visual inspection
• UL 268A listed
• 3-year warranty
NOT a substitute for an open area smoke detector,
NOT a substitute for early warning detection, and
NOT a replacement for a building’s regular fire
detection system.
System Sensor DH400ACDC 4-wire duct housing will
accommodate either the 1451DH ionization sensor or the
2451 photoelectronic sensor. The twist-in, twist-out
Refer to NFPA 72 and 90A for additional duct detector
application information.
Specifications
Length:
Width:
14.5 inches (37 cm.)
5 inches (12.7 cm.)
4 inches (10.2 cm.)
4.5 lbs. (2.0 kg.)
Operating
Humidity Range:
Air Duct Velocity:
10% to 93% relative humidity
500 to 4000 ft./min.
Depth:
Weight:
Operating
Temperature Range:
32° to 120°F (0° to 49°C)
APPROVED
© System Sensor 8/96
This document is not intended to be used for installation purposes.
A05-201-02