Features
■ RoHS compliant*
■ Wide operating temperature range
(-55 °C to +125 °C )
■ Stable performance over temperature range
■ Long life design
■ Low capacitance
Applications
■ Outdoor communications equipment
■ Equipment exposed to harsh environments
■ Small size
■
UL Recognized
2036-xx-SM-H High Temperature Rated GDT Surge Protector
The Bourns® Model 2036 High Temperature Rated TRIGARD™ Series is a 3-electrode Gas Discharge Tube (GDT) Surge Protection
device. The surface mount device provides robust performance and balanced protection in a small 5 mm diameter package. The
Model 2036 High Temperature Series provides stable and long term performance over a wide temperature range, making it ideal for
applications and equipment exposed to harsh environments.
Characteristics
Test Methods per ITU-T K.12, IEEE C62.31 and IEC 61643-311 GDT standards.
Model No.
Characteristic
2036-09
2036-15
2036-23
2036-35
2036-47
2036-60
(1) (2)
DC Sparkover ±25 % @ 100 V/s
90 V
150 V
230 V
350 V
470 V
600 V
(3)
Impulse Sparkover
100 V/μs
1000 V/μs
250 V
550 V
350 V
500 V
450 V
600 V
600 V
750 V
750 V
950 V
850 V
1100 V
Impulse Transverse Delay.................................................1000 V/μs..............................................................< 75 ns
10
Nominal Insulation Resistance (IR)...................................100 V (50 V for Model 2036-09)............................10 Ω initially
Glow Voltage .....................................................................10 mA....................................................................~ 70 V
Arc Voltage........................................................................1 A.........................................................................~ 10 V
Glow-Arc Transition Current.............................................................................................................................< 0.5 A
Capacitance.......................................................................1 MHz....................................................................< 2 pF
(4)
DC Holdover Voltage ....................................................>135 V, (52 V for Model 2036-09, .........................< 150 ms
80 V for Model 2036-15)
(5)
(6)
Nominal Impulse Discharge Current .............................20000 A, 8/20 μs
..............................................1 operation
10000 A, 8/20 μs...................................................10 operations
200 A, 10/1000 μs ................................................300 operations
2000 A, 10/350 μs.................................................1 operation
2
Alternating Discharge Current...........................................20 Arms, 1 s .........................................................1 operation
10 Arms, 1 s ..........................................................10 operations
Storage Temperature........................................................................................................................................-55 to +125 °C
Operating Temperature.....................................................................................................................................-55 to +125 °C
Climatic Category (IEC 60068-1)......................................................................................................................55/125/21
Moisture Sensitivity Level.................................................................................................................................1
.................................................................................................................................6
Notes:
(1)
In ionized mode
At delivery AQL 0.65 Level II, DIN ISO 2859
Impulse sparkover value is defined as typical values of distribution
Network applied per ITU K.12
Total current through center electrode, half value each end electrode to center electrode
DC Sparkover limit may exceed +25 %; GDT will continue to protect as designed
(2)
(3)
(4)
(5)
(6)
•
•
•
•
•
Line to Line voltage is approximately 1.8 to 2 times the stated Line to Center electrode breakdown voltage values
Bourns recommends soldering surface mount devices per IPC/JEDEC J-STD-020 rev. D
Test methods per ITU-T K.12, IEEE C62.31 and IEC 61643-311 GDT standards
8
DC Sparkover limits after life ±25 % (-25 %,+30 % for Model 2036-09 and 2036-60), IR >10
UL Recognized component, UL File E153537
Ω
WARNING Cancer and Reproductive Harm - www.P65Warnings.ca.gov
*RoHS Directive 2015/863, Mar 31, 2015 and Annex.
Specifications are subject to change without notice.
Users should verify actual device performance in their specific applications.
The products described herein and this document are subject to specific legal disclaimers as set forth on the last page of this document, and at www.bourns.com/docs/legal/disclaimer.pdf.