描述
Rack-mounted DCS Signal Conditioners 18K-RACK

18KPR-11-R/S 数据手册

 浏览型号18KPR-11-R/S的Datasheet PDF文件第2页浏览型号18KPR-11-R/S的Datasheet PDF文件第3页浏览型号18KPR-11-R/S的Datasheet PDF文件第4页 
MODEL: 18KPR  
Rack-mounted DCS Signal Conditioners 18K-RACK  
[3] OPTIONS  
Power Switch  
blank: None  
PULSE SCALER  
Functions & Features  
/S: With power switch  
• Takes pulse measurements from turbine meters or  
volumetric flowmeters and outputs in convenient  
engineering unit  
CAUTION  
1) This unit's output waveform is not uniform due to its  
• Module can be retracted without removing wiring for an  
insulation test  
scaling method.  
2) Use input relays which do not cause chattering (e.g.  
mercury relays). Other relays could be used only with a CR  
filter, for 10 Hz at maximum.  
• Optional power switch  
3) Use M-System’s Model M2PRU instead of this unit in  
conjunction with the pulse output from M-System’s power  
transducers.  
R
C = 1 µF  
R = 10kΩ  
PULSE  
SCALER  
Relay  
C
MODEL: 18KPR–[1][2]–R[3]  
GENERAL SPECIFICATIONS  
Construction: Rack-mounted; terminal access via screw  
terminals on the front and connector on the rear; terminal  
cover provided  
ORDERING INFORMATION  
Code number: 18KPR-[1][2]-R[3]  
Specify a code from below for each [1] through [3].  
(e.g. 18KPR-11-R/S)  
Connection  
Input: M3.5 screw terminals (torque 0.8 N·m)  
and connector  
• Input Range (e.g. 0 - 356.7 Hz)  
• Output Range (e.g. 0 - 1.00 Hz)  
Output: M3.5 screw terminals (torque 0.8 N·m)  
and connector  
Power: Supplied from connector  
[1] INPUT  
1: Dry contact (max. 100 kHz)  
Screw terminal: Nickel-plated steel  
Isolation: Input to output to power  
2: Voltage pulse (max. 100 kHz)  
Input pulse sensing: Capacitor coupled; detecting pulse rise  
Sensitivity adjustment: Single-turn screwdriver adjustment  
(front); 25 mVp-p – 5 Vp-p  
[2] OUTPUT  
1: Open collector (max. frequency 20 kHz)  
2: 5 V pulse (max. frequency 20 kHz)  
3: Relay contact (max. frequency 2 Hz)  
4: 24 V pulse (max. frequency 20 Hz)  
Scaling factor adjustment: 10-position rotary switch; 0.9999  
× 10 – 0.0001 × 10–6  
0
POWER INPUT  
DC Power  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
18KPR SPECIFICATIONS  
ES-0460 Rev.1 Page 1/4  
http://www.m-system.co.jp/  

与18KPR-11-R/S相关器件

型号 品牌 描述 获取价格 数据表
18KPR-12-R MSYSTEM Rack-mounted DCS Signal Conditioners 18K-RACK

获取价格

18KPR-12-R/S MSYSTEM Rack-mounted DCS Signal Conditioners 18K-RACK

获取价格

18KPR-13-R MSYSTEM Rack-mounted DCS Signal Conditioners 18K-RACK

获取价格

18KPR-13-R/S MSYSTEM Rack-mounted DCS Signal Conditioners 18K-RACK

获取价格

18KPR-14-R MSYSTEM Rack-mounted DCS Signal Conditioners 18K-RACK

获取价格

18KPR-14-R/S MSYSTEM Rack-mounted DCS Signal Conditioners 18K-RACK

获取价格