MODEL: 18KTS
Rack-mounted DCS Signal Conditioners 18K-RACK
OUTPUT 1
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)
THERMOCOUPLE CONVERTER
Functions & Features
• For thermocouple inputs
[2] OUTPUT 2
• 5-segment linearization, isolation and burnout protection
(outputs scale out when disconnected) included
• High-accuracy cold junction compensation
• Module can be retracted without removing wiring for an
insulation test
Current
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)
POWER INPUT
DC Power
Typical Applications
• High-accuracy cold junction compensation benefits narrow
span measurements
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• 0.1 μA burnout sensing enables long distance
transmission with minimum offset drifts
• Electric furnace (isolation)
[3] OPTIONS
Burnout
• No burnout type can connect to a single T/C in parallel
with a recorder
blank: Upscale burnout
/BL: Downscale burnout
/BN: No burnout
GENERAL SPECIFICATIONS
Construction: Rack-mounted; terminal access via screw
terminals on the front and connector on the rear; terminal
cover provided
Connection
Input: M3.5 screw terminals (torque 0.8 N·m)
and connector
MODEL: 18KTS–[1]6[2]–R[3]
Output 1: Connector
Output 2: M3.5 screw terminals (torque 0.8 N·m)
and connector
ORDERING INFORMATION
• Code number: 18KTS-[1]6[2]-R[3]
Specify a code from below for each of [1] through [3].
(e.g. 18KTS-266-R/BL)
Power input: Supplied from connector
Screw terminal: Nickel-plated steel
Isolation: Input to output 1 to output 2 to power
Overrange output: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
Linearization: Standard
• Temperature range (e.g. 0 - 800°C)
[1] INPUT THERMOCOUPLE
1: (PR) (Usable Range 0 to 1760°C, 32 to 3200°F)
2: K (CA) (Usable range -270 to +1370°C, -454 to +2498°F)
3: E (CRC) (Usable range -270 to +1000°C, -454 to +1832°F)
4: J (IC) (Usable range -210 to +1200°C, -346 to +2192°F)
5: T (CC) (Usable range -270 to +400°C, -454 to +752°F)
6: B (RH) (Usable range 0 to 1820°C, 32 to 3308°F)
7: R (Usable range -50 to +1760°C, -58 to +3200°F)
8: S (Usable range -50 to +1760°C, -58 to +3200°F)
N: N (Usable range -270 to +1300°C, -454 to +2372°F)
0: Specify
Cold junction compensation: CJC sensor attached to the field
terminals
18KTS SPECIFICATIONS
ES-0412 Rev.1 Page 1/4
http://www.m-system.co.jp/