Features
■ Protects subscribers and equipment from
destructive power crosses and lightning
surges
■ Compact size fits subscriber network in-
terface devices
■ Reduces cost of network maintenance
U
■
Listed per 497 C
®
L
■ Patent # 5,508,873 (U.S.);
#2,169,604 (Canada)
■ Reduces frequency of service calls
■ Increases reliability of network operation
1740 Series – Coaxial Surge Protector
75 Ohm Powered & Unpowered Coax DC to >1 GHz
The Bourns 1740 Series of Primary Broadband Coaxial Surge Protectors is designed for Network and other high frequency
applications. The 1740 Series provides protection against surges on 75 ohm coax subscriber drops and has a fail-short
mechanism in the event of dangerous power-crosses. The protector will pass bi-directional signals over the bandwidth from
DC to in excess of 1 Ghz. Its cast-metal housing and environmentally sealed design will withstand the toughest Outside Plant
Applications.
Characteristics
Min. Band Width/Frequency Characteristics
............................................
DC to 1.0 GHz
DC to 1.25 GHz
..................................
Connectors, Input & Output
F-Type (female)
F-Type (female)
Characteristic Impedance ............................................... 75 Ω ......................................................... 75 Ω
Transmission/Insertion Loss (Max.) ................................ 0.15 dB............................................... 0.45 dB
Return Loss (Max.)..................................................... 20 dB.................................................. 13 dB
VSWR (Max.) ............................................................. 1:1.22 ................................................. 1:1.57
Min Fail-Short, Power Cross & Sustained
60 Hz Current Capability
1000 Vrms Open-Circuit Voltage, 25 °C..................... 30 Arms Line to Ground..................... 15 minutes
60 Arms Line to Ground
120 Arms Line to Ground
350 Arms Line to Ground
5 seconds
5 seconds
200 mseconds
Capacitance ............................................................... 1 MHz, 1 Vrms, 0 Vdc ........................ <10 pF
Insulation Resistance ................................................. 100 V.................................................. >108 Ω
Operating Temperature .............................................. -40 °C to 65 °C (-40 °F to 149 °F) ...... -40 °C to 65 °C (-40 °F to 149 °F)
Storage Temperature.................................................. -55 °C to 85 °C (-67 °F to 185 °F) ...... -55 °C to 85 °C (-67 °F to 185 °F)
SURGE PROTECTION CHARACTERISTICS
Typical Impulse Service Life, Lightning
IMPULSE RESET
Model
No.
DC Breakdown
@ 100 V/Sec (Volts)
Service Life, AC, 60 Hz
5A
52.5Vdc
@ 260 mA 135 Vdc
@ 200 mA
Breakdown
@ 100 V/µs
(Volts)
100 A
10/1000 µs
(Operations)
5 kA
20 kA
10 A
8/20 µs
8/20 µs
1000 Vac 1 sec 1000 Vac 1 sec
(Millisec)
(Operations) (Operations)
(Operations)
(Operations)
1740-15
1740-23
1740-35
150 ±20 %
230 ±20 %
350 ±20 %
350
450
650
>1000
>1000
>1000
>10
>10
>10
>1
>1
>1
20
20
20
10
10
10
<150
<150
<150
Product Dimensions
MILLIMETERS
(INCHES)
DIMENSIONS:
F TYPE CONNECTOR
3/8-32 THREAD
81.28
(3.20)
12.70
(.50)
55.88
(2.20)
12.70
(.50)
38.10
(1.50)
9.40
(.37)
19.05
(.75)
REV. L
Specifications are subject to change without notice.