Bu s s m a n n
Square Body – Acce s s orie s
Fuse Bases (Blocks)
DIN 4 3 6 5 3 Fus e Ba s e s
DIN 43 653
For the Typower ZILOX fuses according to DIN 43 653, the
following fuse bases are available:
Part
Number
170H3003
170H3004
170H3005
170H3006
Max.
Voltage
1000V
1000V
1400V
1400V
Rated
Current
630A
1250A
630A
Center
Distance
80mm
80mm
110mm
110mm
1250A
The fuse bases rated 1250A can also be used for the fuses
with higher rated current if the maximum load current is
derated according to the table below:
Fuse Rating
1400A
Max. Load Current In Fuse Base
1325A
1400A
1500A
1650A
1800A
1500A
1600A
1800A
2000A
DIN 43 653
Fixed Center
Base Style
Max. Fuse
Current Rating
Fuse
Size
Max. Voltage
1000V
170H1007
170H1013
400A
200A
00, 000
660V
0000,000
U.L. Recognized to U.L. 512.
Unive rs a l Fus e Ba s e s
For the Typower ZILOX fuses according to DIN 43 653,
French style and North American style, the following fuse
bases are available:
Modular
Base Style
1BS101
Max. Fuse
Current Rating
100A
BIF
Document
1206
Max. Voltage
600V
1BS102
600V
400A
1207
1BS103
600V
400A
1208
1BS104
600V
600A
1209
BH-0xxx
BH-1xxx
BH-2xxx
BH-3xxx
700V
100A
400A
400A
700A
1200
1201
1202
1203
2500V
5000V
1250V
Universal
Modular fuse bases are U.L. Recognized to U.L. 512 and
meet the spacing requirements of U.L. 347. Contact
Bussmann sales representative for more complete ordering
information.
DIN 4 3 6 2 0 Fus e Ba s e s
For fuse bases used with Typower ZILOX fuses according to
DIN 43 620, please contact your local Bussmann sales
representative.
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann
Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to
clearly present comprehensive product data and provide technical information that will help the end user with
design applications. Bussmann reserves the right, without notice, to change design or construction of any
products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change
or update, without notice, any technical information contained in this bulletin. Once a product has been
selected, it should be tested by the user in all possible applications.
Form No.
Page 1 of 1
BIF Doc #720036
7-11-01
SB01191