Phase Failure Relays
WILMAR™ Protective Relays – 1000 Series
Function:
47
• ANSI/IEEE C37.90-1978
• UL file No. E58048
• CSA file No. LR61158
TERMINAL STRIPS
#6 - 32 SCREWS
Phase failure relays protect motors, equipment and
personnel from damage or injury caused by open
phase, reversed phase sequence, or low voltage in a
three phase system. Models are available for 50 and
60 Hz with voltages up to 575 volts. Motor control
switchboards are a common application.
Operation:
The contacts of the relay will close only when it
senses normal conditions of three phase power at
the proper phase sequence.
13
3
/16
The relay contacts will remain in their normally open
position (de-energized) when voltage with incorrect
phase sequence is applied, one or more phases are
open, or at undervoltage condition.
11
/64" DIA.
4 MTG. HOLES
PART NUMBER SELECTION
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
PART NUMBER SELECTION
Sample Part No.
1004X
Type:
1001 = 120 V, 60 Hz, 3 phase,L-L
1007 = 208 V, 60 Hz, 3 phase, L-L
1002 = 230 V, 60 Hz, 3 phase,L-L
1012 = 300 V, 60 Hz, 3 phase, L-L
1013 = 350 V, 60 Hz, 3 phase, L-L
1003 = 380 V, 50 Hz, 3 phase, L-L
1004 = 460 V, 60 Hz, 3 phase,L-L
1005 = 525 V, 60 Hz, 3 phase,L-L
1006 = 575 V, 60 Hz, 3 Phase, L-L
Mounting:
PRODUCT SPECIFICATIONS
Part Number
1000 Series
Nominal Voltage .............................
Voltage Drop-Out ...........................
Pick-Up to Drop-Out Differential ....
Ambient Operating Temperature ....
Temperature Drift ...........................
Time Delay .....................................
Output Contacts .............................
Contact Ratings ..............................
See Table
75% to 100% of nominal, screwdriver adjustable
3% approx.
-40oC to +70oC
X = Flange
± 1%
Blank - Stud
See Curve
Consult factory for additional models and options
One set, normally open
10 amp at 28 VDC resistive
10 amp at 230 VAC resistive
Notes:
1.
Remove screw for access to the undervoltage
adjustment.
2. Clockwise rotation of the adjustment
potentiometer will raise the drop-out voltage.
30