•ꢀ Premium-gradeꢀ90ºCꢀEP
•ꢀ
SIZESꢀ14ꢀTHROUGHꢀ1ꢀAWGꢀ-ꢀCAROLꢀ
SUPER VU-TRON®ꢀ(SIZE)ꢀ(STRANDING)ꢀ
90°CꢀDLOꢀ2000ꢀVOLTSꢀP-7K-123040ꢀ
MSHAꢀCSAꢀR90ꢀ1000Vꢀ(UL)ꢀRHHꢀORꢀRHWꢀ
600ꢀVOLTS
ꢀ
•ꢀ
SIZESꢀ1/0ꢀTHROUGHꢀ646.4ꢀ-ꢀCAROLꢀ
SUPERꢀVU-TRON®ꢀ(SIZE)ꢀ90°CꢀDLO
2000ꢀVOLTSꢀP-7K-123040ꢀMSHAꢀCSAꢀR90ꢀ
1000Vꢀ(-40°C)ꢀFT-1ꢀ(UL)ꢀRHHꢀORꢀRHWꢀ600ꢀ
VOLTSꢀSUNLIGHTꢀRESISTANTꢀFORꢀCTꢀ
USE
NOTE:ꢀ535.3ꢀANDꢀ646.4ꢀkcmilꢀPRINTEDꢀ
(UL)ꢀRHHꢀORꢀRHWꢀ2000ꢀVOLTS
SIZESꢀ777.7ꢀTHROUGHꢀ1111.1ꢀkcmil -
CAROL SUPER VU-TRON® C(UL) TYPE
RHW-2 2KV VW-1 FOR CT USE TYPE DLO
2000Vꢀ90°CꢀP-102ꢀMSHA
2
130
150
170
195
225
260
296
326
362
400
445
493
546
602
635
295
ꢀ
•ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
•ꢀ
•ꢀ
•ꢀ
•ꢀ
•ꢀ
•ꢀ
Dieselꢀelectricꢀlocomotives
Telecomꢀpowerꢀsupply
Miningꢀandꢀearth-movingꢀequipment
Shipyards
Motorꢀleads
Whereꢀflexibleꢀpowerꢀleadsꢀmustꢀbeꢀ
installed in conduit or raceways
•ꢀ
•ꢀ
•ꢀ
•ꢀ
•ꢀ
Excellentꢀimpactꢀandꢀabrasionꢀresistance
Resistsꢀoils,ꢀacids,ꢀalkalies,ꢀheat,ꢀflame
Flexibleꢀtinnedꢀcopperꢀstranding
FT4ꢀuponꢀrequest
Sunlight-resistant
•ꢀ Lengthsꢀcutꢀtoꢀorder
ꢀ
•ꢀ
14ꢀAWGꢀthroughꢀ1111.1ꢀkcmilꢀstrandedꢀ
tinned annealed copper per AAR 589
Mining
Industrial-Grade Cable
Super Vu-Tron® EPR/CPE Diesel Locomotive Cable
90ºCꢀ2000ꢀVoltꢀDLO,ꢀULꢀRHH/RHWꢀ600ꢀVoltsꢀCSAꢀR90ꢀ1000ꢀVolt
Product Construction:
Conductor:
Insulation:
Jacket:
•ꢀ ChlorinatedꢀPolyethyleneꢀ(CPE),ꢀblack
14 AWG - 1111.1 kcmil DLO - 2000 VOLT
Jacket Marking:
COND.
SIZE
CATALOG (AWG/
NUMBER kcmil)
NOM. INS.
CURRENT
AMPS
APPROX.
NET WEIGHT
LBS/MFT(S)
THICKNESS
NOMINAL O.D.
COND.
STRAND
INCHES
mm
INCHES
mm
(1)
(2)
14
12
19/0.0147
19/0.0185
27/24
0.045
0.047
0.045
0.060
0.060
0.060
0.060
0.080
0.080
0.080
0.080
0.080
0.095
0.095
0.095
0.095
0.120
0.120
0.120
0.120
0.140
1.14
1.19
1.14
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.41
2.41
2.41
2.41
3.05
3.05
3.05
3.05
3.56
0.21
0.24
0.26
0.34
0.40
0.46
0.52
0.65
0.69
0.73
0.81
0.87
1.00
1.06
1.10
1.23
1.34
1.45
1.50
1.67
1.84
5.44
6.10
25
35
34
45
81914
81912
81910
81908
81906
81904
81902
81901
81911
81920
81930
81940
81926
81931
81937
81944
81953
81964
81977
81929*
81999
30
40
40
55
10
6.60
60
8
37/24
8.64
55
80
95
6
61/24
10.16
11.68
13.21
16.51
17.53
18.54
20.57
22.10
25.40
26.92
27.94
31.24
34.04
36.83
38.10
42.42
46.74
75
105
140
190
220
260
300
350
405
467
522
591
652
728
815
904
1014
1115
145
4
105/24
154/24
224/24
280/24
329/24
456/24
551/24
650/24
777/24
925/24
1110/24
1332/24
1609/24
1924/24
2299/24
2745/24
95
205
1
440
1/0
515
Applications:
2/0
580
3/0
770
4/0
930
262.6
313.3
373.7
444.4
535.3
646.4
777.7
929.2
1111.1
1130
1295
1545
1820
2195
2560
3050
3625
4354
Features:
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
•ꢀ 90ºCꢀtemperatureꢀrating
Industry Approvals:
ꢀ
ꢀ
•ꢀ ULꢀListed
•ꢀ Acceptedꢀforꢀlistingꢀasꢀflame-resistantꢀ
by MSHA
•ꢀ CSAꢀR90
•ꢀ RoHSꢀCompliant
Dimensions and weights are nominal; subject to industry tolerances.
(1) Ampacitiesꢀbasedꢀonꢀ90°Cꢀconductorꢀandꢀ30°CꢀambientꢀtemperatureꢀbasedꢀonꢀtheꢀNationalꢀElectricalꢀCode® for not more
ꢀ
ꢀ
than three current-carrying conductors in raceway, cable or earth.
(2) Ampacitiesꢀbasedꢀonꢀsingle-conductorꢀinꢀfreeꢀair,ꢀ90°Cꢀconductorꢀtemperatureꢀandꢀanꢀambientꢀairꢀtemperatureꢀofꢀ30°C,ꢀinꢀ
accordance with National Electrical Code® (NEC).
(S) Actual shipping weight may vary.
* Non-stock item
Packaging:
ꢀ