XW4H, XW4L
● Wiring Terminal Blocks
Directly Connecting Wires
(1) Use wires with conductors that are within the connectible wire
range.
(2) Prepare the ends of the wires as shown below.
Refer to Ratings and Specifications for the wire stripping length.
● Terminal Block Connection Method
Using Crimp Terminals
(1) Use ferrules or tab terminals.
However, the Terminal Blocks are small, so sufficiently confirm
the following before you use them.
(2) Insulation between Crimp Terminals
If you use naked crimp terminals, there will be no finger protection.
Also, there will be limited clearance and creepage distances
between adjacent terminals, so use crimp terminals with care.
1mm
6
● Special Screwdriver for Terminal Blocks
Use the XW4Z-00A Special Screwdriver to connect the Terminal
Blocks.
(3) Do not presolder the ends of the wires. Doing so will prevent
correct connections.
You can also use any screwdriver with the following dimensions.
If you use any screwdriver other than the Special Screwdriver or one
with the following dimensions, the Terminal Block may be damaged.
● Connection Methods
Using Ferrules or Solid Wire
Connection Method
Removal Method
(Unit: mm)
Release holess
A
A
0.4
2 dia.
Terminal insertion holes
9
Just press the ferrule all
Insert the screwdriver
the way in.
into the release hole
and pull out the ferrule.
2
Using Stranded Wires
40
Using Stranded Wires
To insert a stranded wire, insert a screwdriver
into the release hole and then insert the wire.
To remove a stranded wire, insert a screwdriver
into the release hole and then pull out the wire.
Note: Do not apply excessive force to the Terminal Block when you
insert the tool. The Terminal Block may be damaged.
• Application examples provided in this document are for reference only. In actual applications, confirm equipment functions and safety before using the product.
• Consult your OMRON representative before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad
systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems or equipment that may have a serious
influence on lives and property if used improperly. Make sure that the ratings and performance characteristics of the product provide a margin of safety for the system or
equipment, and be sure to provide the system or equipment with double safety mechanisms.
Note: Do not use this document to operate the Unit.
OMRON Corporation
Electronic and Mechanical Components Company
Contact: www.omron.com/ecb
Cat. No. G090-E1-03