Analog Addressable Duct Smoke Detectors

XP95-IDR 数据手册

 浏览型号XP95-IDR的Datasheet PDF文件第2页 
XP95-PD/-PDR,  
XP95-ID/-IDR  
Description  
Analog Addressable Duct  
Smoke Detectors  
The Gamewell-FCI analog addressable duct smoke detec-  
tors provide early detection of smoke and products with  
combustion present in air moving through an HVAC duct.  
Fans, blowers and complete systems may be shut down or  
activated in fire alarm mode by the Fire Alarm Control  
Panel (FACP) in the event of smoke detection.  
The Gamewell-FCI analog addressable duct smoke detec-  
tors may utilize either interchangeable photoelectric or ion-  
ization sensor heads. The external alarm indication is a  
light-emitting diode (LED), easily visible through the hous-  
ing. A manual reset switch is provided on the front of the  
sensor.  
XP95 Series  
Duct smoke detectors are also available with auxiliary relay  
contacts. The relay requires two additional wires for power  
and will activate when the sensor reaches alarm levels. All  
wiring must comply with local codes and regulations.  
Features  
Compatible with the Gamewell-FCI 600 Series analog  
addressable control panels  
Interchangeable “Plug-in” photoelectric or ionization  
heads  
XP95 Duct Smoke Detectors digitally transmit their address  
and the chamber’s analog value to the FACP for analysis.  
Address is stored in the sensor base  
Address is set by XPert addressing card  
Remote alarm LED option  
Two-wire supply- polarity insensitive  
Very low standby current  
LED alarm indication on sensor head  
Rugged steel backbox with clear plastic cover  
Large terminal connection screws  
No additional screens or filters to clean or replace  
Relay version available with optional remote test unit  
Three standard tube lengths available: 2.5, 5, or 10 ft.  
(0.762, 1.524, or 3.048 m)  
Air sampling is accomplished by two tubes which protrude  
into the duct. An exhaust tube of one standard length 7.5"  
(19.05 cm) is provided with the sensor housing. Intake sam-  
pling tubes, which must be ordered separately, are supplied  
in three standard lengths: 2.5, 5, or 10 feet  
(0.762, 1.524, or 3.048 m).  
Installation  
Duct mounting is accomplished by the use of a template  
and four sheet metal screws, provided. The duct detectors  
are compatible with the analog loops on Gamewell-FCI’s  
600 Series Analog Addressable Control Panels.  
Programming  
The only programming required for the XP95 Duct Smoke  
Sensors is address setting. This is accomplished through  
the use of the XPert addressing card which is inserted into  
the sensor base.  
An ISO 9000-2000 Company  
SIGNALING  
FM  
MEA  
Approved  
73-92-E  
APPROVED  
3242-1004:103 (photo)  
3242-1004:102 (ion)  
268A  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.  
©2007 by Honeywell International Inc. All rights reserved.  
www.gamewell-fci.com  
CS-2049 Rev. a1 page 1 of 2  

与XP95-IDR相关器件

型号 品牌 描述 获取价格 数据表
XP95-LI GAMEWELL-FCI Analog XP95 line isolator with mounting base

获取价格

XP95-M GAMEWELL-FCI Multi-Sensor

获取价格

XP95-P GAMEWELL-FCI Analog Addressable Duct Smoke Detectors

获取价格

XP95-PD GAMEWELL-FCI Analog Addressable Duct Smoke Detectors

获取价格

XP95-PDR GAMEWELL-FCI Analog Addressable Duct Smoke Detectors

获取价格

XP95-T GAMEWELL-FCI Analog Addressable Thermal Sensor

获取价格