KILLARK LIGHTING
VE3Q / VE4Q SERIES
COMPACT FLUORESCENT EMERGENCY FIXTURES
VE3Q/VE4Q
Class I, Div. 2, Groups A,B,C,D j
Class l, Zone 2, Groups IIC, llB, llA
Class II, Div. 1 & 2, Groups E,F,G
Class III
NEMA 3, 4, 4X
IP66
Class I, Zone 2 AEx nAnR k
Class I, Zone 2 Ex nR k
FEATURES-SPECIFICATIONS
Standard Materials
Accessories
Applications
• Ballast tank and splice box – copper-free
aluminum alloy with baked powder epoxy/
polyester finish, electrostatically applied.
External hardware – 316 SS.
• VEXA100B 3–sided Exit sign: (Use w/o
guard)
CERTILITE® VEQ Emergency Lighting
fixtures provide continuous illumination
under normal power and switch to
emergency battery backup during power
outages. Emergency Units ONLY are
available that operate only when normal
power fails.
•
VEXA400 4–sided Exit sign: (Use w/o guard)
• VMPSD40 Dome and VMPA40 Angle
Reflectors (see page L125)
Compliances
• XCS-OB3-PTT “Push-To-Test” n.c Stantion
(order SWB box separately)
• UL1598 Standard for luminaires
• UL1598A Marine type luminaire
Units contain battery unit(s) that provides
the OSHA required 90 minutes of
illumination for egress.
• UL-844 Standard for lighting fixtures for
Options
hazardous locations
• RD - Red paint housing, mount, guard
(VMAG17, VMAG25S)
• CSA C22.2 no. 137-M1981 electric
luminaries for use in hazardous locations
VExQ units are designed for general and
task lighting in indoors or outdoors where
flammable gases or vapors, combustible
dusts, or simultaneous presence may exist
and create a hazardous location, as defined
by the NEC.
• F, FF - Factory fused; F = Single fuse for
120V, 230V 50 Hz (VExQ); FF = Double
fuse for 208V, 220V 60 Hz, 240V
• UL-924 Emergency Lighting
• Enclosed and gasketed
• NEMA 3, 4X IP66
Note: VE3x dimensions are the same as VM3
VE4x dimensions are the same as VM4
See L128-L129 for more information
• UL 60079-15 - Electrical apparatus for
Explosive Gas Atmospheres with Type of
Protection “n” (Restricted Breathing and
non-sparking).
Use Push-To-Test station suitable for area of
use for testing purposes.
Photometrics similar to VQ1F Series.
Features
FEATURES
BENEFITS
• Quad-Pin triple-tube (VExQ) long-life
• Stainless-to-Stainless securement
com-pact fluorescent lamps included
Swing-Barrel Nut
Patented Tank
Mounting System
• Takes load off during installation
• World Voltage on Quad-Pin VExQ Series:
120 through 277VAC; 50 through 60 Hz
• Uses ordinary tools
• Saves time and labor
Sealed Optic Zone 2
AEx nAR Restricted
Breathing (suffix NR)
• LED charging indicator light visible
through lens
NO External Seals. Lower T-codes, Suitable for Class I Div. 2 Classified
areas per the NEC®. See L84 for more information.
• Pre-wired terminal block for easy power
All glass refractors
Compact (5-1/2” thread size, types I & V)
Standard (7-3/4”, thread size,types I, III, V)
Enhances user selection flexibility
connection
I
III
V
• Two lamp models include two independent
redundant systems
Easier Maintenance, saves labor, move fixture from the ladder to the
workbench
“EZ” mount adapter
• Six mounting splice box types - Pendant,
Ceiling, Wall bracket, Cone Top, 25° Angle
Stanchion, Straight Stanchion.
Photo controls -Class Available as Field or Factory Installedto save energy when light not
I Div. 2 / N4X areas required. For AC ballast only.
• Normally shipped as components for
fast delivery, or may be ordered factory
assembled.
Earthquake Tab -
Built-in attachment Safety: hand” accessories for lamp change out. See L83 for more
point for safety cables information.
Secures fixture to structure in case of conduit failure. “3rd
• Options for Fuses and Quick Disconnect
SEE WWW.HUBBELL-KILLARK.COM LIGHTING SOFTWARE FOR LATEST LED PHOTOMETRY
L209