Industrial Power Supplies  
TSP Series  
90–600 Watt  
Input Specifications  
Input voltage range  
85–132/87–264 VAC autoselect  
– output current derating at operation below 100 VAC see graph B, page 5  
Input voltage frequency  
Harmonic limits  
Holdup time  
47 – 63 Hz  
EN 61000-3-2, Class A (for limited output power)  
20 ms min. (full load 115/230 VAC)  
Inrush current  
115 VAC  
– TSP 070/090 < 12 A  
– TSP 140/180 < 13 A  
– TSP 360 < 16 A  
230 VAC  
< 20 A  
< 25 A  
< 25 A  
< 30 A  
– TSP 600 < 25 A  
Recommended circuit breaker,  
characteristic C  
– TSP 070/090  
– TSP 140/180  
6.0 A  
6.0 A  
or fuse, slow blow type  
– TSP 360 10.0 A  
– TSP 600 15.0 A  
Efficiency  
87% typ.  
Output Specifications  
Output voltage adj. range  
12 VDC models: 12 – 14 VDC  
– 24 VDC models: 24 – 28 VDC  
– 36 VDC model: 36 – 42 VDC  
– 48 VDC models: 48 – 56 VDC  
At output voltage higher than nominal output voltage  
max. output current has to be reduced accordingly, in  
order not to exceed max. output power.  
Regulation  
– Input variation  
– Load variation (10–100 %)  
0.5 % max.  
0.5 % max.  
Ripple and Noise (20MHz Bandwidth)  
100 mV pk-pk typ. (200 mV pk-pk max. at Imax)  
Electronic short circuit protection  
current limitation at Imax.  
constant current, automatic recovery  
Output overvoltage protection  
12 VDC models: 20 V  
– 24 VDC models: 35 V  
– 36 VDC model: 43 V  
– 48 VDC models: 60 V  
Overload protection  
electronic overload protection  
switch off at overtemperature, automatic restart  
12 VDC models: 16 V  
Overtemperature protection  
Power back immunity  
– 24 VDC models: 35 V  
– 36 VDC model: 48 V  
– 48 VDC models: 63 V  
Status indicator  
dual color LED (green: DC ok, red: DC off)  
Power OK signal  
– trigger threshold:  
12 VDC models: 9–11 V  
– 24 VDC models: 18–22 V  
– 36 VDC models: 27–34 V  
– 48 VDC models: 36–46 V  
12 VDC models: 11.0 V 1.0 V  
(20 mA max. for TSP 070, 40 mA max. for TSP 140)  
– 24 VDC models: 22.0 V 2.0V / 20 mA max.  
(10 mA max. for TSP 090, 20mA max. for others)  
– active output signal:  
(reference to –Vout)  
– 36 VDC model: 34.0 V 2.0V / 20 mA max.  
– 48 VDC models: 44.0 V 4.0V / 15mA max.  
DC OK = contact closed  
– relay output  
rated: 30 VDC/1.0 A for 12/24 VDC models  
rated: 30 VDC/2.0 A for 36 VDC model  
rated: 48 VDC/0.5 A for 48 VDC models  
http://www.tracopower.com  
Page 3 of ꢀ3  

与TSP180-148相关器件

型号 品牌 描述 获取价格 数据表
TSP180A FCI THYRISTOR SURGE PROTECTOR SMB TYPE SURFACE MOUNT

获取价格

TSP180AL FCI THYRISTOR SURGE PROTECTOR AXIAL LEAD TYPE

获取价格

TSP180ALL FCI nullLOW CAPACITANCE THYRISTOR SERIES CAPACITANCE THYRISTOR SERIES

获取价格

TSP180B FCI THYRISTOR SURGE PROTECTOR SMB TYPE SURFACE MOUNT

获取价格

TSP180BL FCI THYRISTOR SURGE PROTECTOR AXIAL LEAD TYPE

获取价格

TSP180BLL FCI nullLOW CAPACITANCE THYRISTOR SERIES CAPACITANCE THYRISTOR SERIES

获取价格