TPP 100A-J Series, 100 Watt
Input Specifications
Input Voltage
- AC Range
- DC Range
85 - 264 VAC (Full Range)
120 - 370 VDC (Designed for, no certification)
Input Frequency
Input Current
47 - 63 Hz
550 mA max.
1'150 mA max.
300 mW max. (Ready to meet ErP directive)
60 A max.
0.95 min. (Active Power Factor Correction)
0.95 min. (Active Power Factor Correction)
- Full Load & Vin = 230 VAC
- Full Load & Vin = 115 VAC
- at no Load
- at 230 VAC
- at 230 VAC
Power Consumption
Input Inrush Current
Power Factor
- at 115 VAC
Input Protection
T 3.15 A / 250 VAC (Internal Fuse in L & N)
Output Specifications
Output Voltage Adjustment
10% (By trim potentiometer)
Output power must not exceed rated power!
Voltage Set Accuracy
Regulation
1% max.
0.2% max.
0.5% max.
- Input Variation (Vmin - Vmax)
- Load Variation (0 - 100%)
Ripple and Noise
12 VDC model: 120 mVp-p typ. (with 10 µF X7R)
(20 MHz Bandwidth)
15 VDC model: 150 mVp-p typ. (with 10 µF X7R)
24 VDC model: 160 mVp-p typ. (with 1 µF X7R)
28 VDC model: 180 mVp-p typ. (with 1 µF X7R)
36 VDC model: 190 mVp-p typ. (with 1 µF X7R)
48 VDC model: 340 mVp-p typ. (with 0.1 µF X7R)
12 VDC model: 6'950 µF max.
15 VDC model: 4'450 µF max.
24 VDC model: 1'750 µF max.
28 VDC model: 1'280 µF max.
36 VDC model: 770 µF max.
48 VDC model: 430 µF max.
Not required
Capacitive Load
Minimum Load
Temperature Coefficient
Hold-up Time
0.02 %/K max.
16 ms min.
16 ms min.
1'000 ms max.
- at 230 VAC
- at 115 VAC
- at 230 VAC
- at 115 VAC
Start-up Time
1'000 ms max.
Short Circuit Protection
Output Current Limitation
Overvoltage Protection
Transient Response
Continuous, Automatic recovery
115 - 150% of Iout max.
115 - 135% of Vout nom.
3% max. (50% to 75% Load Step)
500 µs typ. (50% to 75% Load Step)
- Response Deviation
- Response Time
Safety Specifications
Safety Standards
- IT / Multimedia Equipment
IEC 60950-1
EN 60950-1
UL 60950-1
- Medical Equipment
EN 60601-1
IEC 60601-1
ANSI/AAMI ES 60601-1
2 x MOPP (Means Of Patient Protection)
www.tracopower.com/overview/tpp100a-j
Class I Prepared: Connection to PE
Class II Prepared: Reinforced Insulation
PD 2
- Certification Documents
Protection Class
Pollution Degree
Over Voltage Category
OVC II
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
www.tracopower.com June 4, 2019
Page 2 / 4