Current and Voltage Controls
3-Phase Voltage Sequence Control
Type SM 170
• 3-phase monitoring relay for phase
sequence/phase loss
• Measures when all 3 phases are present and
have the correct phase sequence
• Output: 10 A SPDT relay
• Plug-in type module
• S-housing
• LED-indication for power supply and output ON
• Power supply is the 3-phased measuring voltage
Product Description
Ordering Key
SM 170 400
3-phase plug-in monitoring running on only 2 phases or Housing
and phase sequence/phase- to secure the right phase se- Function
loss relay. Frequently used to quence when connecting a Output
prevent a 3-phase motor from load to the mains.
Type
Power supply
Type Selection
Plug
Output
Supply: 220 VAC
SM 170 220
Supply: 380 VAC
SM 170 380
Supply: 400 VAC
SM 170 400
Supply: 415 VAC
SM 170 415
Circular
SPDT
Input Specifications
Output Specifications
Input
Pin 5
Pin 6
Pin 7
Pin 11
Output
SPDT relay
250 VAC (rms)
(cont./elect.)
Phase L1
Phase L2
Phase L3
Neutral (optional connection)
measures on own supply
Rated insulation voltage
Contact ratings (AgCdO)
Resistive loads
µ (micro gap)
AC 1
DC 1
or
10 A/250 VAC (2500 VA)
1 A/250 VDC (250 W)
10 A/25 VDC (250 W)
2.5 A/230 VAC
5 A/24 VDC
≥ 30 x 106 operations
Small inductive loads AC 15
DC 13
Supply Specifications
Power supply AC types
Rated operational voltage
Through pins 5, 6, 7 & 11
Mechanical life
Electrical life
Overvoltage cat. III (IEC 60664)
(IEC 60038)
AC 1
≥ 2.5 x 105 operations
(at max. load)
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand volt. 4 kV (1.2/50 µs) (cont./elect.)
(IEC 60664)
≤ 7200 operations/h
220
380
400
415
3 x 220 VAC ± 15%, 45 to 65 Hz
3 x 380 VAC ± 15%, 45 to 65 Hz
3 x 400 VAC ± 15%, 45 to 65 Hz
3 x 415 VAC ± 15%, 45 to 65 Hz
≥ 2 kVAC (rms) (cont./elect.)
Internal measuring circuit is
connected to pins 5 & 7
Voltage interruption
Dielectric voltage
Rated impulse withstand volt.
≤ 40 ms
None (supply/elect.)
4 kV (1.2/50 µs) (line/neutral,
line/line), direct connection
to electronics
Rated operational power
2.5 VA
Specifications are subject to change without notice
1