MODEL: R7FN-RS4
EX-FACTORY SETTING
Remote I/O R7 Series
/SET: Preset according to the Ordering Information Sheet
(No. ESU-7808-RS4)
FLEX NETWORK I/O MODULE
(RTD input, 4 points, isolated)
RELATED PRODUCTS
Functions & Features
• PC configurator software (model: R7CON)
The configurator software is downloadable at M-System’s
web site.
• 4 points RTD input module for FLEX NETWORK
• Input sensor type can be selected with the front DIP
switches for all channels.
A dedicated cable is required to connect the module to the
PC. Please refer to the users manual for the PC configurator
for applicable cable types.
• Easy parameter setting of individual channels with M-
System's configurator software
• Screen editor software (model: GP-Pro EX)
Screen editor software GP-Pro EX (Ver.2.70 or higher) is
available.
FLEX NETWORK is registered trademark of Digital
Electronics Corporation in Japan.
For versions between 2.60 and 2.70, the driver must be
installed. The driver is downloadable at Digital Electronics
Corporation's web site. http://www.proface.co.jp/
115 (4.53)
53 (2.09)
GENERAL SPECIFICATIONS
Connection: M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal: Refer to the drawing at the end of the
section.
54 (2.13)
mm (inch)
• Communication cable
Recommended manufacture: Japan Solderless Terminal
MFG.Co.Ltd
MODEL: R7FN–RS4-R[1]
Applicable wire size: 0.2 to 0.5 mm
2
(AWG 26 to 22)
ORDERING INFORMATION
• Code number: R7FN-RS4-R[1]
Specify a code from below for [1].
(e.g. R7FN-RS4-R/Q)
• Others
Recommended manufacture: Japan solderless terminal
MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size: 0.25 to 1.65 mm
2
(AWG 22 to 16)
• Specify the specification for option code /Q
(e.g. /C01/SET)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
Isolation: Input 0 to input 1 to input 2 to input 3 to FLEX
NETWORK to power to FG
I/O TYPE
Zero adjustments: Configurable via R7CON
Span adjustments: Configurable via R7CON
Conversion rate: Configurable via R7CON
Burnout setting: Selectable between upscale (*) and
downscale with the front DIP switch
(*) Factory default setting
RS4: RTD input, 4 points
POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Linearization: Standard
RTD Setting: Selectable with front DIP SW or PC
programming.
[1] OPTIONS
Status indicator LED: PWR, RUN
blank: none
(Refer to the instruction manual)
/Q: Options other than the above (specify the specification)
■Recommended solderless terminal
3.3 (.13) max
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
mm (inch)
/C03: Rubber coating
R7FN-RS4 SPECIFICATIONS
ES-7808-C Rev.0 Page 1/6
http://www.m-system.co.jp/