MODEL: R3-NCIE1
■ REMOTE INPUT
15
0
0
F E D C B A
9 8 7 6 5 4 3 2 1
RX(n+0)
RX(n+1)
Remote READY
Redundant Command Read Back
Module Status
RX(n+2)
RX(n+3)
RX(n+4)
RX(n+5)
RX(n+6)
RX(n+7)
Error Status
Data Error Status
Unused
• RX(n+0) is used as Ready signal, the bit is “1” when this module is in normal.
• Redundant Command Read Back (Opt. code: /W Available only for redundant system PLC by Mitsubishi)
The bit written to RY(n+1)0 reads back to RX(n+1)0.
• Module Status
RX(n+2)0 to RX(n+2)F indicate whether individual I/O modules of R3 series are mounted or not.
The bit corresponding to the mounted slot turns to “1”, and the unmounted slot to “0”
• Error Status
RX(n+3)0 to RX(n+3)F indicate error status for each module of R3 series.
The bit corresponding to such module turns to “1”, as described below.
R3-TSx, R3-RSx, R3-US4 Input burnout.
R3-DA16A input power in error or disconnected
R3-YSx output current error (e.g. load unconnected)
R3-PC16A external power supply in error or disconnected
• Data Error Status
RX(n+4)0 to RX(n+4)F indicate data error status for each module of R3 series.
The bit corresponding to such module turns to “1”, as described below.
Input value is out of -15% to +115%
In the case of R3-US4 (voltage input) input level out of -10% to +110%.
RX(n+2)0, RX(n+3)0, RX(n+4)0
RX(n+2)1, RX(n+3)1, RX(n+4)1
RX(n+2)2, RX(n+3)2, RX(n+4)2
:
slot 1
slot 2
slot 3
:
RX(n+2)F, RX(n+3)F, RX(n+4)F
slot 16
Link devices other than the above are not in use.
■ REMOTE OUTPUT (Opt. code: /W Available only for redundant system PLC by Mitsubishi)
15
0
0
F E D C B A
9 8 7 6 5 4 3 2 1
RY(n+0)
RY(n+1)
Not in use
Redundant Command
RY(n+2)
RY(n+7)
Not in use
R3-NCIE1 SPECIFICATIONS
ES-8287 Rev.3 Page 4/8