Electronic control gear
QUICKTRONIC® PROFESSIONAL, two-lamp version
QTP 2x36/230-240
Page 2
Safety:
- Safety shutdown of the power supply to defective lamps
- Compliance with European standards for safety, operation and EMC
- Overvoltage protective cutout for short-duration voltage surges (DIN VDE 160) and for temporary overvoltages
- Greater fire protection because lamps operate at lower temperatures and luminaires can be constructed to meet the
EN 60598/DIN 60598/DIN VDE 0710 and DIN VDE 0711 standards
- Can be used in emergency lighting systems to DIN VDE 0108.
Families:
- QUICKTRONIC® INSTANT START: the low-cost ECG for applications in which lamps are switched on and off only
infrequently.
Now with constant output, making them suitable for damp-proof luminaires
- QUICKTRONIC® PROFESSIONAL, the universal warm-start ECG with constant output
- QUICKTRONIC® SHORT, the short wide alternative to QUICKTRONIC® PROFESSIONAL.
Ideal for all fluorescent lamps and DULUX® L, particularly in applications with frequent switching.
Applications:
used in modern fluorescent lighting systems in:
- offices, computer centres, department stores/supermarkets
- production facilities with
- long working/lighting hours
- rotating machinery
- hazardous areas
- sound studios, hospitals, factories
- tunnels/underground car parks, emergency lighting.
General:
- Supply voltage: 230V/240V
- Mains frequency: 0/50 to 60 Hz
- Lamp start: warm start within 2 s.
- Radio interference suppression: to DIN VDE 0875/CISPR 15/EN 55015
- Mains harmonics: to DIN VDE 0712 Part 23/IEC 929/IEC 555-2 EN 60929
- Immunity to EN 61547
- Battery voltage may drop to 176 V. Lamps must be ignited at over 198 V however. 100 % luminous flux in dc
operation.
- Approx. 0.1 s restart time after a changeover interruption of < 0.2 s
- The luminous flux value for QTP 1x36/230-240, QTP 1x58/230-24, QTP 2x36/230-240, QTP 2x58/230-24 are 96% of
the luminous flux of the choke/starter circuit