PI6-1P / PI6-1T / PI6-OC
Subminiature Electromagnetic and Solid State Modules
• Width 6,2 mm
• Interface relays PI6-1P - with SPDT contact
output / PI6-1T with triac output
• 35 mm rail mount
• Maybe linked with interconnection strip type ZG20
• Equipped in green LED
E105728
PI6-1P*
PI6-1T
PI6-OC
Contact data
Number and type of contacts
Contact material
SPDT
SPST(1NO)
SPST(1NO)
AgSnO
2
Max. switching voltage
Min. switching voltage
Rated load
400 V AC / 250 V DC
10 V
6 A / 250 V AC
400 V / 440 V
20 V
1.2 A / 400 V AC
70 V / 70 V
5 V
AC / DC
AC1
DC1
6 A / 24 V DC; 0.15 A / 250 V DC
100 mA
0.5 A / 70 V DC
1 mA
Min. switching current
Max. inrush current
Max. non-repeat surge current
Rated current
Max. breaking capacity
Min. breaking capacity
Contact resistance
I2t for fusing
10 mA
10 A 20 ms
2
30 A t=20 ms
6A
1500 VA
1 W
1.2 A
0.5 A
AC1
AC1
≤ 100 mΩ 100 mA. 24 V
5.1 A2s t=1-10 ms
50 A/μs
dI/dt
dV/dt
40 V/μs
Max. operating frequency
• at rated load
360 cycles/hour
• no load
72 000 cycles/hour
Input circuit
Rated voltage
DC
12 ... 36 V
5...32 V
5...32 V
AC: 50/60 Hz AC/DC
24 ... 230 V
24 ... 230 V
24 ... 230 V
Turn-off voltage
AC: ≥ 0.2 U ; DC: ≥ 0.1 U
AC : ≥
0.2 U ; DC : ≥
0.1 U
n
n
n
n
Must release voltage
AC: ≥ 0.2 U ; DC: ≥ 0.1 U
n
n
Operating range of supply voltage
Must operate voltage
see page 91
AC and DC: ≤ 0.8 U
n
Rated power consumption
DC
AC/DC
AC/DC
0.3 ... 0.7 W
0.3 ... 1.6 VA / 0.3 ... 1.6 W
0.3 W; 5...32 V DC at 24 V
0.3 VA / 0.3 W; 24 V AC/DC
1.6 VA / 1.6 W; 230 V AC/DC
0.3 W; 5...32 V DC at 24 V
0.3 VA / 0.3 W; 24 V AC/DC
1.0 VA / 1.0 W; 230 V AC/DC
Insulation
Insulation rated voltage
Rated surge voltage
Overvoltage category
Insulation pollution degree
Dielectric strength
• input - output
400 V AC
4 000 V 1.2 / 50 μs
600 V AC
2
600 V AC
2
III
3
4000 V AC 50/60 Hz. 1 min..
type of insulation: reinforced
6000 V 1.2 / 50 μs
4000 V AC 50/60 Hz. 1 min..
type of insulation: reinforced
3000 V AC 50/60 Hz. 1 min..
type of insulation: reinforced
• input - output
• mass - input. output
• contact clearance
2500 V AC 50/60 Hz. 1 min.
1000 V AC 50/60 Hz. 1 min..
type of clearance: micro-disconnection
Input - output distance
• clearance / creepage
≥ 6 mm / ≥ 8 mm
General data
Operating time (typical value)
Release time (typical value)
Electrical life
AC: 7 ms; DC: 6 ms
AC: 15 ms; DC: 10 ms
10 ms max. (zero turn-on)
10 ms max.
5
• resistive AC1
• cos φ = 0.4
• resistive DC1
> 0.6 x 10 ; 6 A. 250 V AC
5
> 2 x 10 ; 2 A. 250 V AC
5
10 ; 6 A. 30 V DC
7
Mechanical life (cycles)
Max. switching frequency
Dimensions (L x W x H)
Weight
> 2 x 10
10 kHz 5...32 V DC (for load up to 24 V DC: 15 kHz)
93.8 x 6.2 x 80 mm
40 g
93.8 x 6.2 x 80 mm
40 g
40g
Ambient temperature
• storage
• operating
Protection category
Environmental protection
-40...+70 °C
AC: -40...+55 °C; DC (12. 24 V): -40...+60 °C
IP 20 PN-EN 60529
-40...+70 °C
-40...+55 °C
IP 20 PN-EN 60529
RTI PN-EN 116000-3
-40...+70 °C
-40...+55 °C
IP 20 PN-EN 60529
RTI PN-EN 116000-3
RTI PN-EN 116000-3
* UL Recognized
90
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
DATA SUBJECT TO CHANGE WITHOUT NOTICE