PET2000-12-074xA
3
General Condition: TA = 0… 55 °C, unless otherwise noted.
PARAMETER
Vi nom Nominal Input Voltage
DESCRIPTION / CONDITION
Rated Voltage High Line (Vi nom HL
Rated Voltage Low Line (Vi nom LL
MIN
200
100
180
90
NOM
230
MAX
240
127
264
140
13
UNIT
)
VAC
VAC
VAC
VAC
)
115
Normal operating (Vi min HL to Vi max HL), High Line
Normal operating (Vi min LL to Vi max LL), Low Line
Vi =100 VAC, I1 = 83 A, ISB = 5 A
Vi
Input Voltage Ranges
Vi = 200 VAC, I1 =167 A, ISB = 5 A
12
Ii max
Maximum Input Current
Vi = 200 VAC, I1 = 145 A, ISB = 5 A
Vi = 220 VAC, I1 = 158 A, ISB = 5 A
Vi = 230 VAC, I1 = 167 A, ISB = 5 A
Vi min to Vi max, TNTC = 25°C, 5 ms
10
ARMS
10
10
Ii inrush
fi
Inrush Current Limitation
Input Frequency
10
Ap
Hz
47
0.8
0.9
0.9
0.95
50/60
0.88
63
Vi = 230 VAC, 10% load
Vi = 230 VAC, 20% load
Vi = 230 VAC, 50% load
Vi = 230 VAC, 100% load
TBD
W/VA
W/VA
W/VA
W/VA
%
0.95
PF
Power Factor
0.997
0.999
THD
Vi on
Vi off
Total Harmonic Distortion
Turn-on Input Voltage2
Turn-off Input Voltage2
TBD
90
Ramping up
87
82
90
91
94
91
18
9
VAC
VAC
%
Ramping down
87
Vi = 230 VAC, 10% load
Vi = 230 VAC, 20% load
Vi = 230 VAC, 50% load
Vi = 230 VAC, 100% load
Vi = 230 VAC, 50% load, 0°
Vi = 230 VAC, 100% load, 0°
Vi = 90 to 264 VAC, 0 to 100% load
91.6
93.8
94.4
92.8
%
Efficiency3
η
%
%
ms
TV1 holdup
Hold-up Time V1
Hold-up Time VSB
ms
TVSB holdup
70
ms
4.1 INPUT CONNECTOR
PET2000-12-074NA power supply is available in 3 different input connector configurations. The versions with IEC 60320-C14
and IEC 60320-C16 have a limited current of 10 A for areas outside North America, in addition the IEC 60320-C14 has a
limited component temperature of 70°C. The Anderson Saf-D-Grid® has no limitation with respect to both current and
temperature.
The PET2000-12-074NA power supply is available with IEC 60320-C14.
Below table shows the maximum rated operating conditions for the different input connector options. The applied operating
condition must remain within these conditions to allow safety compliant operation.
See also 10.3 MAXIMUM OUTPUT POWER VERSUS INLET TEMPERATURE FOR SAFETY COMPLIANCY for detailed
derating curves.
2 The Front-End is provided with a minimum hysteresis of 3 V during turn-on and turn-off within the ranges
3 Efficiency measured without fan power per EPA server guidelines