描述
Universal input

LPS41-T 技术参数

生命周期:Transferred零件包装代码:MODULE
包装说明:,针数:10
Reach Compliance Code:unknownECCN代码:EAR99
风险等级:5.55Is Samacsys:N
其他特性:IT OPERATES FROM AN AC SUPPLY OF 85V TO 264V模拟集成电路 - 其他类型:AC-DC REGULATED POWER SUPPLY MODULE
最大输入电压:300 V最小输入电压:120 V
JESD-30 代码:R-XXMA-X10最大负载调整率:2%
功能数量:1输出次数:1
端子数量:10最高工作温度:50 °C
最低工作温度:最大输出电压:3.63 V
最小输出电压:3.135 V标称输出电压:3.3 V
封装主体材料:UNSPECIFIED封装形状:RECTANGULAR
封装形式:MICROELECTRONIC ASSEMBLY认证状态:Not Qualified
表面贴装:NO技术:HYBRID
温度等级:COMMERCIAL端子形式:UNSPECIFIED
端子位置:UNSPECIFIED最大总功率输出:55 W
微调/可调输出:YESBase Number Matches:1

LPS41-T 数据手册

 浏览型号LPS41-T的Datasheet PDF文件第2页浏览型号LPS41-T的Datasheet PDF文件第3页 
Embedded Power for  
Business-Critical Continuity  
Rev. 07.23.07  
LPS40-M Series  
1 of 3  
LPS40-M Series  
40 Watts  
RoHS  
Medical  
Total Power:  
40-55 Watts  
Input Voltage: 85-264 VAC  
120-300 VDC  
# of Outputs:  
Triple  
Electrical Specifications  
Input  
Special Features  
• Medical safety approvals  
• Universal input  
• 3" x 5" footprint  
• Less than 1U high  
Input range  
Frequency  
Inrush current  
Input current  
Efficiency  
85-264 VAC; 120-300 VDC  
47-440 Hz  
<18A peak @ 115VAC; <36A peak @ 230VAC, cold start @ 25°C  
1A max. (RMS) @ 115VAC  
70% typical at full load  
• Remote sense on main output  
• Low output ripple  
EMI filter  
FCC Class B conducted; CISPR 22 Class A conducted;  
EN55022 Class A conducted; VDE 0878 PT3 Class A conducted  
<75μA @ 50/60 Hz, 264 VAC input  
• Adjustable 5V output  
• Overvoltage protection  
• Overload protection  
• 110 KHz switching frequency  
• LPX40 enclosure kit available  
Safety ground  
leakage current  
Output  
Maximum power  
Adjustment range  
Hold-up time  
40W for convection; 55W with 30CFM forced air  
-5, +10% minimum  
20ms @ 40W load, 115VAC nominal line  
Overload protection  
Short circuit protection on all outputs  
Case overload protected @ 110-145% above peak rating  
Overvoltage protection 5V output; 5.7 to 6.7VDC. Other outputs 10% to 25%  
above nominal output  
Remote sense  
Compensates for 0.5 V lead drop minimum.  
Will operate without remote sense connected.  
Reverse connection protected.  
Safety  
VDE  
UL  
0750/EN60601-1 (IEC601)  
UL2601 E182560  
CSA 22.2 No.601.1  
LR109492  
CSA  
CE Mark (LVD)  

与LPS41-T相关器件

型号 品牌 获取价格 描述 数据表
LPS42 ASTEC

获取价格

40 Watts
LPS42 EMERSON-NETWORKPOWER

获取价格

Universal input
LPS42-M EMERSON-NETWORKPOWER

获取价格

Medical safety approvals
LPS42-M ASTEC

获取价格

40 Watts Medical
LPS42-T EMERSON-NETWORKPOWER

获取价格

Universal input
LPS42-T ASTEC

获取价格

40 Watts
LPS43 EMERSON-NETWORKPOWER

获取价格

Universal input
LPS43 ASTEC

获取价格

40 Watts
LPS43-M ASTEC

获取价格

40 Watts Medical
LPS43-M EMERSON-NETWORKPOWER

获取价格

Medical safety approvals