100W Single Output LED Power Supply
HVGC-100 series
Features :
Constant current design
Wide input range 180~480VAC
Built-in active PFC function
High efficiency up to 91%
Protections: Short circuit / Over voltage / Over temperature
Cooling by free air convection
OCP point adjustable through output cable or internal potentiometer
IP67 / IP65 design for indoor or outdoor installations
Class 2 power unit
Three in one dimming function (0~10Vdc or 10V PWM signal or resistance)
Suitable for LED lighting and street lighting applications
Compliance to worldwide safety regulations for lighting
Suitable for dry / damp / wet locations
5 years warranty (Note.6)
110
F
M
M
IP65 IP67
HVGC-100-350
A
A : IP65 rated. Output voltage and constant current level can be adjusted through internal potentiometer.
B : IP67 rated. Constant current level adjustable through output cable with 0~10Vdc or 10V PWM signal or resistance.
D (option) : IP67 rated. Timer dimming function, contact MEAN WELL for details.
SPECIFICATION
MODEL
HVGC-100-350
HVGC-100-700
RATED CURRENT
350mA
5.0%
700mA
CURRENT ACCURACY
MAX. OUTPUT VOLTAGE
RATED POWER
3 ~ 285V
99.75W
3 ~ 142V
99.4W
OUTPUT
RIPPLE & NOISE (max.) Note.2 1Vp-p
0.5Vp-p
Can be adjusted by internal potentiometer or through output cable
210 ~ 350mA
CURRENT ADJ. RANGE
420 ~ 700mA
SETUP, RISE TIME
3000ms, 150ms at full load 440VAC / 347VAC ; B type 5000ms, 150ms at 95% load 440VAC / 347VAC
30ms at full load 440VAC / 347VAC
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.3 180 ~ 480VAC
47 ~ 63Hz
PF 0.98/230VAC, PF 0.98/277VAC, PF 0.97/347VAC, PF 0.94/440VAC at full load (Please refer to "Power Factor Characteristic" curve)
254VDC ~ 679VDC
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
INPUT
91%
91%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
0.32A / 347VAC
0.26A / 440VAC
COLD START 50A / 440VAC
<0.75mA / 440VAC
Constant current limiting, recovers automatically after fault condition is removed
300 ~ 320V
Protection type : Shut down o/p voltage with auto-recovery or re-power on to recovery
100 10 (RTH2)
SHORT CIRCUIT
OVER VOLTAGE
150 ~ 160V
PROTECTION
ENVIRONMENT
OVER TEMPERATURE
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-40 ~ +70 (Refer to "Derating Curve")
WORKING TEMP.
20 ~ 95% RH non-condensing
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-40 ~ +80 , 10 ~ 95% RH
0.03%/ (0 ~ 50
)
10 ~ 500Hz, 5G 12min./1cycle, period for 72min. each along X, Y, Z axes
UL8750, CSA C22.2 No. 250.0-08, TUV EN61347-1, EN61347-2-13, IP65 or IP67 approved ; design refer to UL60950-1, TUV EN60950-1
I/P-O/P:3.75KVAC I/P-FG:1.88KVAC O/P-FG:0.5KVAC
SAFETY STANDARDS Note.4
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
SAFETY &
EMC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55015, EN61000-3-2 Class C ( 50% load) ; EN61000-3-3, FCC part 15 class B
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61547, light industry level (surge 4KV), criteria A
EMC IMMUNITY
MTBF
186.1Khrs min. MIL-HDBK-217F (25
236*68*38.8mm (L*W*H)
)
OTHERS
NOTE
DIMENSION
PACKING
1.18Kg; 12pcs/15.2Kg/0.74CUFT
1. All parameters NOT specially mentioned are measured at 347VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 2.2uf parallel capacitor.
3. Derating may be needed under low input voltages. Please check the static characteristics for more details.
4. Safety and EMC design refer to EN60598-1, CNS15233, GB7000.1.
5. The power supply is considered as a component that will be operated in combination with final equipment. Since EMC performance will be affected by the
complete installation, the final equipment manufacturers must re-qualify EMC Directive on the complete installation again.
6. Refer to warranty statement.
File Name:HVGC-100-SPEC 2012-03-20