MODEL: HSP
Voltage
Space-saving Plug-in Signal Conditioners H-UNIT
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3: 0 – 1 V DC (Load resistance 1000 Ω min.)
4: 0 – 10 V DC (Load resistance 10 kΩ min.)
5: 0 – 5 V DC (Load resistance 5000 Ω min.)
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
0: Specify voltage (See OUTPUT SPECIFICATIONS)
LOW FREQUENCY TRANSMITTER
(50 Hz minimum)
Functions & Features
• Converting the output from a pulse-type transducer into a
standard process signal
• Excitation
• High-density mounting
POWER INPUT
DC Power
Typical Applications
R: 24 V DC
• Positive displacement flowmeters, turbine flowmeters and
vortex flowmeters
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Proximity switches
[3] OPTIONS
26 (1.02)
blank: none
/Q: With options (specify the specification)
93
(3.66)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
137
(5.39)
/C02: Polyurethane coating
mm (inch)
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
MODEL: HSP–[1][2]–R[3]
GENERAL SPECIFICATIONS
Construction: Plug-in
ORDERING INFORMATION
• Code number: HSP-[1][2]-R[3]
Specify a code from below for each of [1] through [3].
(e.g. HSP-2A-R/Q)
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless
steel
• Frequency range (e.g. 0 – 10 kHz)
• Special output range (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01/S01)
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange output: 0 to 120 % at 1 – 5 V
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
Input pulse sensing: DC coupled; detecting pulse rise
Low-end cutout: 2 to 5 %
[1] INPUT
1: Dry contact
2: Voltage pulse
[2] OUTPUT
Current
A: 4 – 20 mA DC (Load resistance 750 Ω max.)
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)
D: 0 – 20 mA DC (Load resistance 750 Ω max.)
E: 0 – 16 mA DC (Load resistance 900 Ω max.)
F: 0 – 10 mA DC (Load resistance 1500 Ω max.)
G: 0 – 1 mA DC (Load resistance 15 kΩ max.)
Z: Specify current (See OUTPUT SPECIFICATIONS)
HSP SPECIFICATIONS
ES-3456 Rev.9 Page 1/3
http://www.m-system.co.jp/