General Specifications Genesys™ GENH750W
2.1 INPUT CHARACTERISTICS
1. Input voltage/freq. (*1)
2. Power Factor
85~265Vac continuous, 47~63Hz, single phase
0.99 @100/200Vac, rated output power.
Complies with EN61000-3-2 class A and EN61000-3-3 at 20~100% output power.
750W :10.5A / 5A,
3. EN61000-3-2,3 compliance
4. Input current 100/200Vac
5. Inrush current 100/200Vac
6. Hold-up time
750W :Less than 25A,
More than 20mS, 100Vac, at 100% load.
2.2 POWER SUPPLY CONFIGURATION
1. Parallel Operation
2. Series Operation
Up to 4 units in master/slave mode with single wire current balance connection
Up to 2 units. with external diodes.
600V Max to Chassis ground
2.3 ENVIRONMENTAL CONDITIONS
1. Operating temp
2. Storage temp
3. Operating humidity
4. Storage humidity
5. Vibration
6. Shock
7. Altitude
0~50°C, 100% load.
-20~70°C
30~90% RH (non-condensing).
10~95% RH (non-condensing).
MIL-810E, method 514.4, test cond. I-3.3.1. The EUT is fixed to the vibrating surface.
Less than 20G, half sine, 11mSec. Unit is unpacked.
Operating: 10000ft (3000m), Derat output current by 2%/100m above 2000m, Non operating: 40000ft (12000m).
2.4 EMC
1. Applicable Standards:
2. ESD
IEC1000-4-2. Air-disch. -8KV, contact disch. -4KV
IEC1000-4-4. 2KV
3. Fast transients
4. Surge immunity
5. Conducted immunity
6. Radiated immunity
7. Conducted emission
8. Radiated emission
9. Voltage dips
IEC1000-4-5. 1KV line to line, 2KV line to ground
IEC1000-4-6, 3V
IEC1000-4-3, 3V/m
EN55022B, FCC part 15J-B, VCCI-B.
EN55022A, FCC part 15-A, VCCI-A.
EN61000-4-11
10. Conducted emission
11. Radiated emission
2.5 SAFETY
EN55022B, FCC part 15-B, VCCI-B.
EN55022A, FCC part 15-A, VCCI-A.
1.Applicable standards:
UL 60950-1, CSA22.2 No.60950-1, IEC 60950-1, EN 60950-1
Models with Vout 50V: Output is SELV, all communication/control interfaces (RS232/485, IEEE, Isolated Analog,
LAN, Sense, Remote Programming and Monitoring) are SELV.
Models with 60V Vout 400V: Output is Hazardous, communication/control interfaces: RS232/485, IEEE,
Isolated Analog, LAN, Remote Programing and Monitoring (pins 1-3, pins14-16) are SELV, Sense, Remote
Programming and Monitoring (pins 8-13, pins 21-25) are Hazardous.
2.Interface classification
Models with 400V Vout 600V: Output is Hazardous, all communication/control interfaces (RS232/485, IEEE,
Isolated Analog, LAN, Sense, Remote Programming and Monitoring) are Hazardous.
Vout 50V models : Input-Output (SELV): 4242VDC 1min, Input-communication/control (SELV): 4242VDC 1min,
Input-Ground: 2828VDC 1min,
60V Vout 150V models: Input-Output (Hazardous): 3425VDC 1min, Input-communication/control (SELV):
4242VDC 1min, Output(Hazardous)-SELV: 2307VDC 1min, Output(Hazardous)-Ground: 1414VDC 1min,
Input-Ground: 2828VDC 1min.
3.Withstand voltage
300V Vout 600V models: Input-Output(Hazardous): 3490VDC 1min, Input-communication/control (SELV):
4242VDC 1min, Hazardous. Output-communication/control(SELV): 4242VDC 1min,
Output(Hazardous)-Ground: 2738VDC 1min, Input-Ground: 2828VDC 1min.
More than 100Mohm at 25°C , 70% RH.
4.Insulation resistance
2.6 MECHANICAL CONSTRUCTION
1. Cooling
Forced air flow: from front to rear. No ventilation holes at the top or bottom of the chassis; Variable fan speed.
2. Dimensions (WxHxD)
3. Weight
W: 214.0mm, H: 43.6mm, (57.0mm Benchtop version), D: 437.5mm (excluding connectors, encoders, handles, etc.)
7Kg (15 Lbs)
IEC320 AC Inlet.
4. AC Input connector
5. Output connectors
6V to 60V models: Bus-bars (hole Ø 6.5mm). 80V to 600V models: Meating plug, Phoenix P/N: GIC 2.5/4-ST-7.62.
2.7 RELIABILITY SPECS
1. Warranty
5 years.
Also available, Genesys™
1U full Rack 750W/1500W/2400W
2U full Rack 3300W/5000W
GENH | GENESYS™ | 5