Single-Stage Filters FN 2410 and FN 2412
DATASHEET
EMC/RFI Filters for Industrial Electronics
Excellent filter performance for applications
Approvals
with high interference levels
Filters for two-phase supply up to 2x 520 VAC
(P-P) available
Fast and comfortable snap-in installation on
popular TS 35 DIN-rails up to 45 A
Industrial grade terminal blocks for
unsurpassed electrical safety
Features and benefits
FN 2410 filters up to 100 A are designed for
traditional chassis mounting
For extra fast installation, FN 2412 filters up to 45 A
can comfortably be snapped-in on popular TS 35
DIN-rails which are common in most electrical
cabinets
Performance indicators
Both FN 2410 and FN 2412 are also avail- able as „H
versions“. These are ideally suitable for an operation
on two phases in a three-phase power network,
handling voltages up to 520 VAC
All filters provide an exceptional conducted
attenuation performance, based on chokes with
high saturation resistance and excellent thermal
behavior. Thus, all filters retain the expected filter
performance even in very noisy applications and
under full load conditions
Touch-safe industrial grade terminal blocks provide
maximum electrical safety and protect humans
from undeliberate contact with life conductors.
They help to fulfill the most demanding installation
standards
Technical specifications
1x 250 VAC (FN 2410/FN 2412)
Maximum continuous operating voltage
Typical applications
2x 520/300 VAC (FN 2410 H/FN 2412 H)
Small to medium-sized machines and industrial
equipment
DC to 400 Hz
Operating frequency
Rated currents
8 to 100 A @ 50°C (FN 2410)
8 to 45 A @ 50°C (FN 2412)
High-end single-phase power supplies
P –> E 2000 VAC for 2 sec
High potential test voltage
Single-phase variable speed motor drives, inverters
and converters
P –> N 1100 VDC for 2 sec
P –> E 2700 VDC for 2 sec (H types)
P –> P 2250 VDC for 2 sec (H types)
DIN-rail filter versions are ideal for panel building
and electrical cabinets
IP 20
Protection category
Overload capability
Various noisy applications with higher power single-
phase or two-phase supply
4x rated current at switch on,
1.5x rated current for 1 minute, once per hour
-25°C to +100°C (25/100/21)
UL 94 V-2 or better
Temperature range (operation and storage)
Flammability corresponding to
Design corresponding to
Typical electrical schematic
UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939
1,200,000 hours
MTBF @ 50°C/250 V (Mil-HB-217F)
250,000 hours (H types)