EDCC  
Class CC, 600Vac, 0.5 to 30A  
Time-Delay Fuses  
Dimensions (inches)  
• Can be used where either a time-delay or a fast-acting  
fuse is needed, making selection easier and reducing  
spare fuse inventories for substantial cost reduction.  
Catalog Symbol: EDCC  
Time-Delay  
• Superior Motor Protection for small horsepower motor  
circuits.  
Current-Limiting  
Volts: 600Vac (or less)  
300Vdc (or less)  
Amps: 0.5 to 30A  
IR: 200kA RMS Sym.  
• Proper sizing can provide Type “2” coordinated  
protection for NEMA and IEC motor controllers.  
• Motors receive maximum protection against burnout  
from overloads and single phasing.  
20kAIC (0.5 – 2.25A and 20-30A)  
Agency Information: CE, UL Listed, Std. 248-4, Class CC,  
Guide JDDZ, File E162363, CSA Certified, HRCI-CC, C22.2  
No. 248.4, Class 1422-02, File 53787  
Catalog Numbers (amps)  
EDCC0.5  
EDCC0.6  
EDCC0.8  
EDCC1  
EDCC1.125  
EDCC1.25  
EDCC1.4  
EDCC1.6  
EDCC1.8  
EDCC2  
EDCC2.25  
EDCC2.5  
EDCC2.8  
EDCC3  
EDCC4  
EDCC4.5  
EDCC5  
EDCC5.6  
EDCC6  
EDCC6.25  
EDCC7  
EDCC8  
EDCC9  
EDCC10  
EDCC12  
EDCC15  
EDCC20  
EDCC25  
EDCC30  
Features  
• A superior all-purpose, space-saving branch circuit fuse  
that meets most protection requirements up to 30 amps.  
13  
1
• Very compact; physical size is only 32" x 1 ⁄  
2"  
EDCC3.2  
EDCC 3.5  
(10.3 x 38.1mm) with rejection tip.  
EDCC7.5  
• Faster response to damaging short-circuit currents and  
higher interrupting rating than mechanical overcurrent  
protective devices.  
Carton Quantity and Weight  
• Maximum 200kA interrupting rating for available fault  
current in today's large capacity systems. Helps ensure  
that future growth will not obsolete the system.  
Carton  
Quantity  
10  
Weight per Carton  
Amps  
0.5-30  
lbs  
kg  
0.09  
0.19  
• Time-delay to avoid unwanted fuse openings from surge  
currents.  
Class CC Fuse Blocks (600V) Catalog Data  
• Fast speed of response under short-circuit conditions for  
a high degree of current-limitation.  
Screw  
Pressure  
Screw  
Pressure  
Plate  
Box  
Quick-  
Quick-  
Poles Terminal  
Terminal Connect  
Connect  
• The EDCC fuse can be sized close to full load ratings  
for maximum overload and short-circuit protection.  
1
2
3
BC6031S BC6031P BC6031B BC6031SQ BC6031PQ  
BC6032S BC6032P BC6032B BC6032SQ BC6032PQ  
BC6033S BC6033P BC6033B BC6033SQ BC6033PQ  
Form No. EDCC  
Page 1 of 2  
Data Sheet #1300  
07-10-07  
BU-SB07255  

与EDCC30相关器件

型号 品牌 描述 获取价格 数据表
EDCC4 COOPER Electric Fuse, Time Delay Blow, 4A, 600VAC, 300VDC, 200000A (IR), Inline/holder

获取价格

EDCC4.5 COOPER Electric Fuse, Time Delay Blow, 4.5A, 600VAC, 300VDC, 200000A (IR), Inline/holder

获取价格

EDCC5 COOPER Electric Fuse, Time Delay Blow, 5A, 600VAC, 300VDC, 200000A (IR), Inline/holder

获取价格

EDCC5.6 COOPER Electric Fuse, Time Delay Blow, 5.6A, 600VAC, 300VDC, 200000A (IR), Inline/holder

获取价格

EDCC-5006 ASTRODYNE 5W Ultraminiature Encapsulated Switching Power Supplies

获取价格

EDCC-5006DRL ASTRODYNE 5W Ultraminiature Encapsulated Switching Power Supplies

获取价格