DIN Rail Mount

DRH 数据手册

 浏览型号DRH的Datasheet PDF文件第2页 
InstallationDISN RhaileMeoutnt  
PART NUMBER NOMENCLATURE  
Control Voltage  
A: 90-280 VAC/VDC  
D: 4-32 VDC  
Switching Type  
Blank: Zero Voltage Turn-On  
R: Instantaneous Turn-On  
DRH Series 3 Phase  
Function  
Series  
3P: Contactor  
Solid State Contactors  
DRH  
3P  
60  
Operating Voltage  
60: 48-600 VAC  
A
18  
R
DIN Rail Mount  
Rated Load Current  
18: 18 Amps (3 Controlled legs)  
20: 20 Amps (2 Controlled legs)  
This installation sheet includes detailed mounting and wiring instructions which apply  
for Crydom DRH 3 Phase Solid State Contactors. Be sure to visit the product series'  
datasheet available at the Crydom website to complement this information. If you  
have questions or need additional information please contact Crydom Tech Support.  
Required for valid part number  
For options only and not required for valid part number  
Please read all mounting instructions before using your DRH Series Solid State  
Contactor.  
WIRING DIAGRAM(C)  
L1  
L2  
L3  
MOUNTING INSTRUCTIONS (A, B)  
General Use /  
AC-51 Application  
To install on DIN rail  
Install the contactor on the DIN  
rail (as shown in fig.1).  
T1  
T2  
T3  
Wire the contactor to the input  
L1  
L2  
L3  
side. AWG #18 (0.8 mm2)  
To remove from  
minimum, AWG #12 (3.3 mm2) x  
DIN rail  
+A3  
13  
+A1  
2 maximum.  
Wire the contactor to the  
output side. AWG #18 (0.8 mm2)  
DRH3P60xxx  
IND. CONT. EQ.  
minimum, AWG #10 (5.3 mm2) x  
CONTROL  
INPUT  
fig. 1  
2 (stranded/solid) maximum.  
Motor Controller /  
AC-53a Application  
XXXX  
INPUT  
STATUS  
Use copper conductors with at  
least a 75ºC insulation rating.  
T1  
T2  
T3  
fig. 2 Terminal  
screw type.  
Top/Bottom view.  
Recommended strip length is  
10 mm maximum.  
-A4  
14  
-A2  
T1  
T2  
T3  
M
Maximum recommended terminal screw torque input 12 in-lb (1.36 Nm) & output  
15 in-lb (1.7 Nm).  
3
Overload current  
protection needs to  
be considered  
If multiple units are installed be sure to follow derating curves  
T1  
T2  
T3  
WARNING! Removing product from 35 mm rail incorrectly by not using the  
appropriate tool could damage the latching system.  
0.9 in  
[22 mm]  
Minimum  
Important Considerations  
Be sure to use input and output voltages within operating ranges.  
TABLE 1. HP Ratings at Nominal Voltage  
Ambient Temperature  
DRH @ 480 VAC  
5 HP / 3.7 kW  
3 HP / 2.2 kW  
1.5 HP / 1.1 kW  
LED indicates input and alarm status. It does not represent output  
status.  
40ºC  
60ºC  
80ºC  
To achieve maximum ratings, there must be a minimum spacing of  
0.9 in (22 mm) between the devices in free air. (See fig. 3)  
fig. 3 Multiple units mounting  
for maximum ratings  
DERATING CURVES  
DRH3P60x20  
DRH3P60x18  
20  
15  
10  
5
18  
15  
12  
9
Single unit, or multiple units with spacing  
greater than minimum (see fig. 3)  
Multiple units, no minimum spacing  
between components (see fig. 3)  
6
3
0
0
20  
30  
40  
50  
60  
70  
20  
30  
40  
50  
60  
70  
Ambient Temperature (ºC)  
Ambient Temperature (ºC)  
General Notes  
(A) See compatible accessories in corresponding datasheet.  
(B) For optimal thermal performance, contactor vents should be aligned vertically to maximize airflow.  
(C) On models with 2 controlled legs, L2 and T2 are linked internally.  
Rev. 031516  
Do not forget to visit us at: www.crydom.com  
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.  

与DRH相关器件

型号 品牌 描述 获取价格 数据表
DRH_17 CRYDOM DIN Rail Mount

获取价格

DRH-120 MEANWELL 120W Single Output Industrial DIN RAIL Power Supply

获取价格

DRH-120_09 MEANWELL 120W Single Output Industrial DIN RAIL Power Supply

获取价格

DRH-120_11 MEANWELL 120W Single Output Industrial DIN RAIL Power Supply

获取价格

DRH-120-24 MEANWELL 120W Single Output Industrial DIN RAIL Power Supply

获取价格

DRH-120-48 MEANWELL 120W Single Output Industrial DIN RAIL Power Supply

获取价格