Specifications
Performance Specifications
Item
10-point I/O
20-point I/O
30-point I/O
40-point I/O
Control method
Stored program method
I/O control method
Programming language
Instruction word
Combination of the cyclic scan and immediate refresh processing methods.
Ladder diagram
1 step per instruction, 1 to 5 words per instruction
Types of
Basic instructions 14 types
instructions
Special
79 types, 139 instructions
instructions
Instruction
execution time
Basic instructions 0.72 to 16.2 #s
Special
MOV instruction = 16.3 #s
instructions
Program capacity
2,048 words
Maximum I/O
points
CPU only
10 points (6 input/
4 output points)
20 points (12 input/ 30 points (18 input/ 40 points (24 input/
8 output points)
12 output points)
90 points (54 input/ 100 points (60 input/
36 output points) 40 output points)
16 output points)
With Expansion
I/O Unit
---
---
Input bits
00000 to 00915 (Words 0 to 9)
Output bits
01000 to 01915 (Words 10 to 19)
512: IR 20000 to IR 23115 (IR 200 to IR 231)
Work bits (IR Area)
Special bits (SR Area)
Temporary bits (TR Area)
Holding bits (HR Area)
Auxiliary bits (AR Area)
Link bits (LR Area)
384: SR 23200 to SR 25515 (SR 232 to SR 255)
8: TR 0 to TR 7
320: HR 0000 to HR 1915 (HR 00 to HR 19)
256: AR 0000 to AR 1515 (AR 00 to AR 15)
256: LR 0000 to LR 1515 (LR 00 to LR 15)
Timers/Counters
128: TIM/CNT 000 to 127
100-ms timer: TIM 000 to TIM 127
10-ms timer: TIM 000 to TIM 127
Decremental counter, reversible counter
Data memory
Read/Write
Read only
1,024 words (DM 0000 to DM 1023)
512 words (DM 6144 to DM 6655)
Interrupt processing:
External interrupt
2 points (Response 4 points (Response time of 0.3 ms max.)
time of 0.3 ms max.)
Memory protection
Memory backup
Maintains the contents of the HR, AR, Counter and Data Memory Areas.
Flash memory: User program, data memory (Read only) (Non-battery powered stor-
age)
Super capacitor: Data memory (Read/Write), holding bits, auxiliary memory bits, count-
er (20-day storage at an ambient temperature of 25"C)
Self-diagnostic function
Program check
CPU error (watchdog timer), memory errors, I/O bus errors
No END instruction programming errors (constantly checked during operation)
1 point: 2 kHz
Pulse output
High-speed counter
1 point: Single phase at 5 kHz or two-phase at 2.5 kHz (linear counting method)
Incremental mode: 0 to 65535 (16-bit)
Decremental mode:--32767 to 32767 (16-bit)
1 point: Single phase at 5 kHz or two-phase at 2.5 kHz (linear counting method)
Incremental mode: 0 to 65535 (16-bit)
Decremental mode:--32767 to 32767 (16-bit)
Quick-response inputs
Input time constant
Analog settings
Together with the external interrupt input (minimum pulse width of 0.2 ms)
Can be set at 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms, 64 ms, or 128 ms.
2 points: (0 to 200)
Note: Bits that are not used for the I/O bits can be used as work bits.