Surge arrester
B88069X8230B502
T80-A250XF
3-electrode arrester
Features
Applications
Standard size
Fast response time
High current rating
Stable performance over life
Very low capacitance
High insulation resistance
Reliable failsafe device
RoHS-compatible
Branch exchange (MDF)
Line protection
Station protection
Electrical specifications
DC spark-over voltage 1) 2) 3)
250
V
%
V
V
Tolerance
Min.
Max.
±20
200
300
Impulse spark-over voltage 3)
at 100 V/µs - for 99% of measured values
< 500
< 450
V
V
- typical values of distribution
at 1 kV/µs
- for 99% of measured values
- typical values of distribution
< 650
< 600
V
V
Service life
10 operations
1 operation
10 operations [5× (+) & 5× (–)]
1 operation
50 Hz; 1 s 4)
10
A
A
kA
kA
50 Hz; 0.18 s (9 cycl.) 4) 40
8/20 µs 4)
8/20 µs 4)
10
15
3)
Insulation resistance at 100 VDC
> 10
< 1.5
< 0.2
GΩ
pF
µs
Capacitance at 1 MHz 3)
Transverse delay time 5)
Arc voltage at 1 A
Glow to arc transition current
Glow voltage
~ 35
< 1
~ 200
V
A
V
Weight
~ 2.2
g
Operation and storage temperature
Climatic category (IEC 60068-1)
Marking, red negative
°C
−40 ... +125
40/125/21
250 YY O
250
YY
O
- Nominal voltage
- Year of production
- Non radioactive
Certifications
UL 497B (E163070)
Remarks on next page
PPD AB PD / PPD AB PM
Version: 05 / 2019-08-21
Please read Cautions and warnings and
Page 2 of 6
Important notes at the end of this document.