Surge arrester
B88069X1193T603
S20-A470X
2-electrode arrester
Electrical specifications and stress test methods
Nominal DC spark-over voltage 3) 4)
470
30
329
611
V
%
V
V
Tolerance
Min.
Max.
Impulse spark-over voltage
at 100 V/µs
- for 99% of measured values
- typical values of distribution
< 1050
< 950
V
V
at 1 kV/µs
- for 99% of measured values
- typical values of distribution
< 1200
< 1050
V
V
Service life 5))
10 operations [5× (+) & 5× (–)]
10 operations [5× (+) & 5× (–)]
8/20 µs
5/320 µs 6)
0.5
150
kA
A
Insulation resistance at 100 VDC
Capacitance at 1 MHz
> 1
G
< 0.3
pF
Arc voltage at 1 A
Glow to arc transition current
Glow voltage
~ 10
< 0.1
~ 65
V
A
V
)
At delivery AQL 0.65 level II, DIN ISO 2859
4) In ionized mode
5) Tests according to ITU-T Rec. K. 12 and UL 497B
6) DC spark-over voltage values may exceed ±50% after stress, but tubes still operates w/o venting
Terms and current waveforms in accordance with ITU-T Rec. K. 12; IEC 61643-21 and IEC 61643-311.
PPD AB PD / PPD AB PM
Version: 07 / 2021-05-31
Please read Cautions and warnings and
Page 3 of 7
Important notes at the end of this document.