Line reactors, output chokes and output filters
3-phase line reactors for converters
B86305L
Technical data and measuring conditions
Rated voltage VR
Rated current IR
Test voltage Vtest
520 V AC (50/60 Hz)
Referred to 40 °C rated temperature
1100 V DC, 2 s (line/line)
2500 V DC, 2 s (lines/case)
At IR; 50 Hz and 400 V AC
155 (F)
Relative voltage drop vk in %
Insulation class
Overload capability (thermal)
Climatic category (IEC 60068-1)
Approvals
3 ꢁ IR, t < 3 s in 300 s
25/100/21 (ꢀ25 °C/+100 °C/21 days damp heat test)
Insulation system class 155 (F)
Characteristics and ordering codes
1)
2)
3)
IR*)
A
Ordering code
Terminal cross section
mm2
Rtyp
mΩ
LR
PL
W
Approx. weight
kg
vk
%
mH
VR = 520 V AC
4
7
10
11
16
21
30 10
35 10
46 16
50 16
4
4
4
4
4
4
5.4 335.0
4.0 112.0
10.0
4.2
4.0
2.6
2.0
1.4
1.0
25 1.5
31 2.1
43 2.6
37 2.5
B86305L0004R000
B86305L0007R000
B86305L0010R000
B86305L0011R000
B86305L0016R000
B86305L0021R000
B86305L0030R000
B86305L0035R000
B86305L0046R000
B86305L0050R000
B86305L0060R000
B86305L0075S000
B86305L0100S000
B86305L0156S000
B86305L0230S000
B86305L0390S000
B86305L0600S000
B86305L0800S000
B86305L0900S000
5.4
3.6
4.4
4.0
4.1
4.0
4.0
4.1
4.1
4.1
4.1
4.2
4.7
4.0
4.1
4.1
4.2
78.0
63.0
42.2
24.0
12.4
11.0
8.0
7.8
6.2
5.7
3.2
1.47
0.9
0.46
0.3
0.2
65
62
62
3.0
4.8
5.5
0.84
80 6.6
94 8.5
0.64
0.6
0.5
0.4
0.3
0.2
120 8.4
100 8.5
170 12.0
160 15.0
250 21.5
60 35
75 20 × 3
100 20 × 3
156 20 × 3
230 20 × 3
390 30 × 5
600 40 × 5
800 50 × 5
900 50 × 5
0.15 340 32.0
0.075 400 49.2
0.05 650 65.5
0.038 880 84.5
0.034 990 90.5
0.19
*) Higher current values on request
1) Typical value at 20 °C
2) at IR, Tolerance -0%/+20%
3) at IR, 50 Hz and 20 °C
Please read Cautions and warnings and
Important notes at the end of this document.
Page 3 of 15