Film capacitors – Power Factor Correction
Key components – Hybrid PF-controller
B44066R6066E230/B44066R6466E230
BR6000-T6R6 V6.0
- Internal error storage
Additional Features
- 2nd signal relay random
- Triggering time programmable
Technical data
Weight
1 kg
Case
Panel-mounted instrument, 144 × 144 × 55 mm
(cut out 138 × 138 mm)
Ambient conditions
Overvoltage class
Pollution degree
II
2
Operating temperature
Storage temperature
Sensitivity to inference (industrial areas)
Spurious radiation (residential areas)
Safety guidelines
–20 ... +60 °C
–20 ... +75 °C
EN55082–2.1995
EN55011–10.1997
IEC61010–1:2001, EN61010–1:2001
Any
Mounting position
Humidity class
15 ... 95% without dew
Protection class
Front plate
IP54 to IEC60529
IP20 to IEC60529
Rear side
Operation
Supply voltage
110 … 230 V AC, 50 and 60 Hz power lines
0.3 inductive to 0.3 capacitive adjustable
20 ... 1000 ms / 1 … 1200 s
Target cos ϕ
Switching and discharge time range
(dynamic / static section)
20 series preset + control series editor for free
programming
Number of control series
Control modes
- Series switching (LIFO),
- Circular switching (FIFO),
- Self-optimized intelligent control mode
Measurement
Measurement voltage range
Fundamental frequency
Measurement current (CT)
Minimum operating current
Maximum current
30 ... 525 V AC (L–N) or (L-L)
50 and 60 Hz
x/5 and x/1 Ampere possible
40 mA / 10 mA
5.3 A (sinusoidal)
< 15 ms
Zero voltage release
FILM P PM LMP
May 2012
Please read Cautions and warnings and
Page 3 of 7
Important notes at the end of this document.