Power Quality Solutions
B44066F3075S648
Active Harmonic Filter PQSine™ S Series
3P3W wall mounted / PQSM3075S648
Technical data and specifications AHF system (cont.)
Recommended external AC mains
protection (fuse or circuit breaker)
160 A (for details please see manual)
Mounting
Cooling
Wall
Forced cooling 359 L/sec
Interface
Modbus (RTU),TCP/IP(Ethernet)
Communication ports
Fault alarm
RS485 and network port (RJ45)
Available, max. 500 alarm records
Temperature
-10 … +40 °C for operating temperature (may derate capacity if ambient
temperature exceeds 40°C), -20…+70 °C for storage temperature
Protection class
Panel color
IP20 according to IEC 529
RAL7035 light grey
Humidity
5%~ 95%, non-condensing
Self-protection
Overheating protection
Yes
Yes
Yes
Over-voltage and under-voltage
protection
Typical noise level
Altitude
< 65 dB (depending on model and load conditions)
1% up 1500 m. Between 1500 m to 4000 m, according to GB/T3859.2,
the power decreases by 1% for every additional 100 m.
Standards / recommendations
specifying limits for harmonics in
networks or units
IEEE519, IEC 61000-3-6, ER G5/4
Design standards
IEC 61000-4-2, 4-3/4-4/4-5/4-6/4-8/4-11, IEC 60146, EN 55011 Class A,
EN 50091-1, EN 50178 (type test report available upon request) after
the standard EN 50178
Certificates
CE, ETL (UL/CSA)
CAP FILM PM
August 2018
Please read Cautions and warnings and
Page 4 of 9