4
HIGH PERFORMANCE CBEs AS168X
Technical data (continued)
Add-on modules:
Rated voltage U
AC 277 V
Rated current I
6 A
e
n
Auxiliary contact H1 & H2 and
Signal contact S1 & S2
Functional auxiliary contact module
Type H1 (assumes the same contact position)
Type H2 (assumes the opposite position)
Actuation of the contact is determined
by the condition of the handle position
of the adjacent poles.
Functional signal contact
Relay trip module
Type S1 (assumes the same contact position)
Type S2 (assumes the opposite position)
The signal contact operates due to a
thermal magnetic tripping and must
be reset by hand.
Type
Voltage range AC/DC
Impedance at 50/60 Hz
A1
A2
A3
A4
A5
5 – 12 V
10 – 24 V
20 – 48 V
40 – 110 V
90 – 240 V
1.1 Ω
4.7 Ω
16 Ω
63 Ω
395 Ω
Function of relay trip module
The module allows remote tripping by
applying a voltage between the
terminals. Operating time 8 – 16 ms.
General data:
Dielectric strength
AC 2000 V
Vibration resistance
0,75 mm amplitude, 10 – 57 Hz
Shock resistance
Waveform 11 ms
25 g
IP20
Protection against electric shock
Finger safe per IEC 529
Permissible ambient temperature
Weight
-20°C to +60°C
1 pole
ca. 130 g
ca. 130 g
ca. 100 g
ca. 100 g
ca. 120 g
Switched neutral
Auxiliary contact
Signal contact
Relay trip module