Remote ON/OFF actuation X8345-R for Circuit Breaker 8345
Description
The X8345-R is an additional module which provides remotely controlled
ON and OFF functionality for the E-T-A series 8345 magnetic circuit
breaker range. The module actuator, which is motor driven, is factory
fitted adjacent to the circuit breaker(s) which it is controlling. The module
can be operated by a suitable external changeover switch, momentary
switches (one ON, one OFF). The status of the actuator will follow the
position of the external switch, i.e. if the circuit breaker trips electrically
or is operated manually, the actuator will not change.
A single module will control a single pole breaker or multipole circuit
breakers up to 2 poles. In the application it has to be ensured that the
supply voltage is maintained at all times.
When switching the circuit breaker OFF manually the module has also to
be switched off by means of te changeover switch before switching the
breaker on again. The same is true for normal switch-on of the breaker.
1
X8345-R
US patent number: US 7,532,095 B2
Internal connection diagrams
Ordering information
Type number
X8345 Module for type 8345, 1, 2 pole and 3 pole
ꢉꢋꢃꢄꢜꢅ ꢎꢆꢜꢅꢝ ꢁꢔꢐꢈꢂꢑꢜꢋꢀꢚꢓꢂꢄꢃꢅꢌꢋꢀ ꢎꢈꢆꢌꢅꢀꢌꢋꢆꢃꢝ
ꢊꢋꢌꢁ ꢈꢅꢓꢆꢌꢅ ꢞꢟꢠꢞꢡꢡ ꢂꢀꢌꢑꢂꢌꢋꢆꢃ
ꢍꢆꢎꢅꢈꢂꢌꢅꢐ ꢢꢔ ꢀꢁꢂꢃꢄꢅꢆꢇꢅꢈ ꢉꢊꢋꢌꢀꢁꢒ
Module
R
remote ON/OFF actuation
Operating voltage
ꢀꢁꢂꢃꢄꢅꢆꢇꢅꢈ ꢉꢊꢋꢌꢀꢁ
ꢍꢃꢆꢌ ꢎꢂꢈꢌ ꢆꢏ ꢌꢁꢅ ꢎꢈꢆꢐꢑꢀꢌꢒ
24 DC 24 V
Add-on version
01 mounted on right side
Mounting method
ꢥ
ꢞꢡꢡ
ꢞꢟ -
ꢀ
ꢙꢕꢖꢗ5ꢚꢛ
00 front panel mounting (standard)
02 2-bracket: module and circuit breaker fitted
Terminal design
ꢣ
1
ꢤ
11
01 spring loaded screwless terminal 5-pin
Supply status
ꢕꢖꢗ5 ꢊꢋꢌꢁ ꢘꢋ
M
module mounted to the base unit
1ꢤ 1ꢗ
X8345 - R 24 01 00 01 M
ordering example
ꢉꢋꢃꢄꢜꢅ ꢎꢆꢜꢅꢝ ꢁꢔꢐꢈꢂꢑꢜꢋꢀꢚꢓꢂꢄꢃꢅꢌꢋꢀ ꢎꢈꢆꢌꢅꢀꢌꢋꢆꢃꢝ
ꢊꢋꢌꢁ ꢈꢅꢓꢆꢌꢅ ꢞꢟꢠꢞꢡꢡ ꢂꢀꢌꢑꢂꢌꢋꢆꢃ
ꢍꢂꢀꢌꢑꢂꢌꢅꢐ ꢢꢔ ꢌꢊꢆ ꢓꢆꢓꢅꢃꢌꢂꢈꢔ ꢉꢊꢋꢌꢀꢁꢅꢉꢒ
Technical data
Voltage rating
ON duty
DC 24 V (16...32 V)
50 % / 60 sec
< 2 sec
ꢓꢆꢓꢅꢃꢌꢂꢈꢔ ꢉꢊꢋꢌꢀꢁ
ꢍꢃꢆꢌ ꢎꢂꢈꢌ ꢆꢏ ꢌꢁꢅ ꢎꢈꢆꢐꢑꢀꢌꢒ
Trip time
Blocking current
Control current
Typical life
< 1.5 A
ꢞꢡꢡ
ꢥ
ꢞꢟ -
ꢀ
ꢙꢕꢖꢗ5ꢚꢛ
< 3 mA
ꢣ
10,000 operations (ON/OFF)
-25...70 °C (-13...158 °F)
1
ꢤ
11
ꢕꢖꢗ5 ꢊꢋꢌꢁ ꢘꢋ
Ambient temperature
Insulation co-ordination
(IEC 60664)
2.5 kV/2 (EN 60934)
1ꢤ 1ꢗ
Dielectric strength
pole to module
test voltage AC 1,500 V (EN 60934)
> 100 MΩ (DC 500 V)
Insulation resistance
Vibration
10 g (57-2000 Hz), 0,76 mm (10-57 Hz)
to IEC 60068-2-6, test Fc,
10 frequency cycles/axis
Typical applications
Remote circuit breaker control (ON/OFF) for communication systems,
marine installations, automation equipment and similar requirements.
Shock
100 g (11 ms) to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity
Mass
240 hours at 95 % RH,
to IEC 60068-2-78, test Cab
Caution:
During actuation of the remote control, free travel of the toggle must
be ensured.
approx. 65 g (without base unit)
Preferred types Remote Control
X8345-R-24-01-00-01-M
X8345-R-24-01-02-01-M
1651
www.e-t-a.de
9