Remote trip module X8345-F for Circuit Breaker 8345-...
Description
Dimensions
A module which adds remote trip capability to all versions of type 8345.
A voltage applied across the coil, by means of an external sensor for
example, will cause disconnection of the main switch/circuit breaker
mechanism.
ꢂꢇꢇꢈꢉꢈꢊꢋꢌꢍ ꢎꢏꢐꢊꢉꢏ ꢉꢎꢈꢑ ꢐꢊꢇꢒꢍꢏ
ꢀꢁꢂꢃ
ꢀꢄꢅꢆ
Typical applications
Electrical monitoring of safety systems, remote trip.
1
Ordering information
ꢓꢔꢕꢓ
ꢕꢘ1ꢔ
ꢗꢕꢔ
ꢕꢔꢓꢚ
Type No.
X8345 Module for type 8345
Module
16ꢕꢖ
ꢕ6ꢖ5
16
ꢕ6ꢔ
F
remote trip module
Assembly version
01 only in pole 1
02 only in pole 2
Remote trip version
X1 DC
Internal connection diagram
Voltage rating
24 24 V
1
48 48 V
ꢃꢍꢐꢄ
1ꢀꢁꢂꢃꢄ ꢁꢅꢂꢆꢄꢇꢆꢄꢈ
ꢉꢊꢈꢅꢋꢌꢃꢍꢇꢀꢎꢋꢏꢐꢄꢆꢍꢇꢋꢃꢃꢊ
ꢑꢍꢆꢉ ꢋꢈꢈꢍꢆꢍꢂꢐꢋꢃ
Terminal design
02 blade terminals DIN 4644-A2.8-0.5
ꢅꢄꢎꢂꢆꢄ ꢆꢅꢍꢁ ꢇꢂꢍꢃ
M
module mounted to circuit breaker
X8345 - F 01 X1 24 02
M
ordering example
ꢒ
ꢔꢕ
Preferred types
ꢓ
ꢀ
Preferred types remote trip module:
X8345-F-01-X1-24-02-M
X8345-F-01-X1-48-02-M
Technical data
Voltage ratings and typical internal resistance values
Voltage ratings
DC 12 V; DC 24 V; DC 48 V
approx. 40 W
Power consumption
Pulse operation
Current rating (A)
DC 12 V
Internal resistance (Ω)
20 ms < tON < 100 ms/tOFF > 10 sec
(Continuous duty possible for multipole
devices upon request)
3.4
DC 24 V
13.9
64.3
Typical life
10,000 operations at UN
Ambient temperature
-40...+85 °C (-40...+185 °F)
DC 48 V
Insulation co-ordination
(IEC 60664)
2.5 kV/2 (EN 60934)
test voltage
Dielectric strength
between main circuit
and trip coil circuit
AC 3,000 V (EN 60934)
> 100 MΩ (DC 500 V)
Insulation resistance
Vibration
6 g (57-2000 Hz) 0.46 mm (10-57 Hz)
shock direction 1/2
4 g (57-2000 Hz) 0.30 mm (10-57 Hz)
shock direction 3/4
3 g (57-2000 Hz) 0.23 mm (10-57 Hz)
shock direction 5/6
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
100 g (11 ms)
(not when mounted upside down)
to IEC 60068-2-27, test Ea
Corrosion
Humidity
Mass
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
mm
This is a metric design and millimeter dimensions take precedence (
)
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
inch
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved. Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.
approx. 8.5 g (without base unit)
8
www.e-t-a.de
1651