POWR-GARD® Fuse Datasheet
E-RATED MEDIUM VOLTAGE FUSES
Description
Characteristics
E-rated fuses have time current characteristics designed to
provide current-limiting protection for power transformers,
potential transformers, power centers, feeder centers, and
unit sub stations. When properly applied, they can protect
against high and low fault currents.
Voltage Ratings
Current Range
2,750 V – 38,000 V
10E – 600E
Options
• Hermetically sealed for use in hazardous locations
(add “S” suffix to part number)
NEMA Standards for E-rated medium voltage fuses require
that fuses rated 100E or less open within 300 seconds
(5 minutes) when subjected to an RMS value of 200-240%
of the fuse continuous current rating; and fuses with an
E rating larger than 100E must open within 600 seconds
(10 minutes) when subjected to an RMS current of 220-
240% of the fuse’s continuous current rating. These values
establish one point on the time-current curve.
• Clip-lock (CL) available.
Dimensions
6.38"
9.75"
3"DIA
Application Note
Since these fuses are used for the protection of general
purpose circuits which may contain transformers, motors,
and other equipment producing in-rush and/or overload
currents, fuses should generally be rated at 140% of the
normal full load current, and circuits should be analyzed
to ensure that system load currents will not exceed the
current rating of the fuse.
Dim.A
Clip
Center
Dim.B
Figure 4
Figure 5
Figure 6
ORDERING/CATALOG
MAX INTERRUPTING
RATING RMS (ASYM)*
FIGURE
NUMBER
SIZE
DIM. A (INCHES) DIM. B (INCHES)
E-RATED
NUMBER
10E1C2.75
15E1C2.75
10E
15E
20E
25E
30E
40E
50E
65E
80E
100E
125E
150E
200E
125E
150E
200E
250E
300E
350E
400E
450E
7"
7"
7"
7"
7"
7"
7"
7"
7"
7"
7"
7"
7"
7"
7"
7"
7"
7"
7"
7"
7"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
10.875"
80,000
80,000
80,000
80,000
80,000
80,000
80,000
80,000
80,000
80,000
80,000
80,000
80,000
80,000
80,000
80,000
80,000
80,000
80,000
80,000
80,000
4
4
4
4
4
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
5
20E1C2.75
25E1C2.75
30E1C2.75
40E1C2.75
50E1C2.75
65E1C2.75
80E1C2.75
100E-1C2.75
125E1C2.75
150E1C2.75
200E1C2.75
125E2C2.75
150E2C2.75
200E2C2.75
250E2C2.75
300E2C2.75
350E2C2.75
400E2C2.75
450E2C2.75
* RMS Asymmetrical amperes = RMS Symmetrical amperes x 1.6
© 2016 Littelfuse POWR-GARD® Products
Rev: 120816
4 of 10