MODEL: 73VR1100
INSTALLATION
Power input
•AC:
Approx. 15 VA at 100 V
Approx. 20 VA at 240 V
•DC: 8 W or 340 mA
Operating temperature: 0 to 50°C (32 to 122°F)
Display quality (e.g. decreased contrast) may deteriorate
when the recorder is used for a long time in an environment
exceeding 50°C. However, it is only a temporary
phenomenon. When the recorder is back in normal
temperature, full legibility is recovered. No damage in
performance.
Operating humidity: 30 to 85 %RH (non-condensing)
Allowable dust particles: 0.1 mg/m
2
(no conductive particles)
Corrosive gas: Not allowed
Mounting: Panel flush mounting (except desktop type)
Panel cutout dimensions: 137 × 137 mm (5.39”× 5.39”)
Weight: 1.7 kg (3.7 lb)
Caution: Use of UPS (switching time: without delay, output:
sine waveforms) is recommended to prevent data loss or CF
card damage by a loss of power during recording.
PERFORMANCE
Calendar clock accuracy: Monthly deviation 3 minutes at
25°C
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(alarm output to RUN output to power or FG or RS-485)
AC powered:
2000 V AC @ 1 minute (power to FG or Ethernet or RS-485)
500 V AC @ 1 minute (FG or RS-485 to Ethernet)
DC powered:
1250 V AC @ 1 minute (power to FG or Ethernet or RS-485)
500 V AC @ 1 minute (FG or RS-485 to Ethernet)
STANDARDS & APPROVALS
EU conformity:
(M2 AC power of desktop type does not conform to EU
directive)
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Alarm output to RUN output to power to FG or Ethernet or
RS-485: Reinforced insulation (300 V)
RoHS Directive
73VR1100 SPECIFICATIONS
ES-7399 Rev.24 Page 3/18