5秒后页面跳转
710 PDF预览

710

更新时间: 2024-11-28 12:49:59
品牌 Logo 应用领域
MACOM 继电器
页数 文件大小 规格书
1页 83K
描述
WILMAR™ Protective Relays - 700 Series

710 数据手册

  
Reverse Power Relays  
WILMARProtective Relays 700 Series  
Function:  
32  
ANSI/IEEE C37.90-1978  
UL file No. E58048  
CSA file No. LR61158  
TERMINAL STRIPS  
#6 - 32 SCREWS  
Several types of Reverse Power Relays are available  
including relays sensitive to reverse reactive power  
(KVAR). WILMAR is the leading brand of reverse power  
relays. Our rugged sealed construction provides con-  
tinuous and reliable operation unaffected by shock,  
vibration or other severe environments. Reverse Power  
Relays are used for the protection of generator sets  
operating in parallel.  
3 13  
/16  
80%  
70%  
60%  
50%  
11  
/64  
" DIA.  
4 MTG. HOLES  
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.  
40%  
PART NUMBER SELECTION  
Model 710 (X)  
Designed for 120, 220 or 266 volt  
30%  
20%  
10%  
0%  
Model 720 (X) thru 724 (X)  
For operation on three phase,  
three wire circuits  
line to neutral connection  
0.000  
0.100  
0.200  
0.300  
0.400  
Time Delay (seconds)  
PRODUCT SPECIFICATIONS  
700 Series  
PART NUMBER SELECTION  
Part Number  
Sample Part No.  
710X  
Line Voltage...................................... Model 710X = 120 V, 220 V or 266 V  
Type: ± 20%  
line to neutral sensing  
710 = 120 V, 220 V, 266 V line to neutral  
720 = 120 V, L-L, 3 Phase  
721 = 230 V, L-L, 3 Phase  
722 = 380 V, L-L, 3 Phase  
723 = 460 V, L-L, 3 Phase  
724 = 575 V, L-L, 3 Phase  
725 = 416 V, L-L, 3 Phase  
Mounting:  
Line Frequency ................................. 50-500 Hz.  
Current Requirements ..................... 0 to 5 amp max direct or from CT with 5 amp  
secondary  
Screwdriver adjustable 4% to 20% (of the 5 amp rating)  
Inverse Delay - See Chart  
Trip Adjustment ...............................  
Time Delay ........................................  
X = Flange  
Output Contacts ............................... One set N.O., one set N.C.  
Blank - Stud  
5 amp resistive at 120 AC or 28 Vdc  
Contact Ratings ................................  
Power Consumption ........................  
Options:  
7 = Reverse Inductive  
P = Surge Suppression  
Voltage circuit: 2 VA max.  
Current circuit: 4 VA max.  
Consult factory for additional models.  
Notes:  
1. Remove screw for access to the pick-up adjustment.  
2. Clockwise rotation of the adjustment will raise the reverse trip point.  
3. This relay senses true power, which is a product of voltage, current and phase angle.  
Connections and polarity must be obversed in accordance with the provided diagrams.  
2 8  
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)  

与710相关器件

型号 品牌 获取价格 描述 数据表
71-0.2 SIPAT

获取价格

71MHz SAW Filter 0.2MHz Bandwidth
7100 FILTRAN

获取价格

HDSL Transformer
7100 GILWAY

获取价格

T- Subminiature Lamps
7100.0160.XX SCHURTER

获取价格

Subminiature Fuse, 10 x 10 mm, 125 VAC, 125 VDC
7100.0170.XX SCHURTER

获取价格

Subminiature Fuse, 10 x 10 mm, 125 VAC, 125 VDC
7100.0180.XX SCHURTER

获取价格

Subminiature Fuse, 10 x 10 mm, 125 VAC, 125 VDC
7100.0190.XX SCHURTER

获取价格

Subminiature Fuse, 10 x 10 mm, 125 VAC, 125 VDC
7100.0200.XX SCHURTER

获取价格

Subminiature Fuse, 10 x 10 mm, 125 VAC, 125 VDC
7100.1008.13 SCHURTER

获取价格

Electric Fuse, Time Lag Blow, 0.2A, 250VAC, 250VDC, 35A (IR), Through Hole, ROHS COMPLIANT
7100.1008.XX SCHURTER

获取价格

Subminiature Fuse, 11.5 x 5 mm, Tr®e T