Contactors & Control Relays
Safety Control Relays
700S-P
Specifications
Type
700S-P
10 A @ 600V AC / 5 A @ 600V DC
NEMA A600
Contact Rating Continuous
AC
Ratings
Make/Break
DC
NEMA P600
Min. Contact Switching Ratings
10V, 50 mA
Volts DC
Contacts
in Series
24 64 125 250 500 600
5A 2.2A 1.1A 0.55A 0.24A 0.2A
1
DC Switching
2
10A 10A 5A
2A 0.7A 0.5A
3A 1.5A 1.0A
3
4
—
—
—
—
7A
Features
10A 5A 2.5A 1.5A
•
•
•
•
•
•
•
Mechanically linked contacts meeting IEC 947-5-1-L
2…12 poles – all mechanically linked
1.5 mil. ops. at 10A break at 120V AC
14 mil. ops. at 1A break at 120V AC
6 mil. ops. at 1A break at 24V DC
Contact Electrical Life—
Resistive Loads
Red faceplate for easy identification of safety circuits
IEC mechanically linked contacts symbol displayed on front
Double-break contacts to reduce probability of welded contacts
Visual indication of contact state
Tamper resistant cover helps prevent changes which could
jeopardize safety
AC
85…110%
80…110%
Coil Voltage
DC
Range ➊
Battery
85…115%
Charging
50 Hz
132 VA
19.3 VA
60 Hz
138 VA
19 VA
•
•
Complete Catalogue number displayed on front
Ideal for use in safety circuits
Inrush
Sealed
Inrush
Sealed
Coil
Con-
sump-tion
AC
12.7 W
12.7 W
DC
All contacts are mechanically linked
per IEC 947-5-1 annex L for 2 to 12
poles
Mechanically Linked
Contacts
Pick-up
Dropout
AC – 10…20 ms / DC – 30…50 ms
AC – 10…20 ms / DC – 20…33 ms
12.5 million operations ➊
Operating
Time
Mechanical Life
2 to 12 Poles, Double Break Contacts
N.O. or N.C. (8 N.C. Maximum)
Contact Arrangement
Contact Material/Design
Mounting
Silver Nickel/Bifurcated
Panel mount or mount on 700-MP Rail
Horizontal Mounting Recommended
Operating➊
Storage
–20…+65°C (–4…149°F)
–40…+65°C (–40…149°F)
1X #18 AWG…2X #12 AWG
8…12 lb-in. (0.9…1.4 N•m)
Te m p er atu re
Wire size per UL/CSA
Tightening Torque
➊ Coil voltage required for proper operation (percent of rated coil voltage).
➊ 90% of devices are expected to meet or exceed 12.5 million operations,
and 50% of devices are are expected to meet 20 million operations.
➊ Temperature inside the panel.
9-29