V-EA-Series - UL508 Manual Motor Controller - 3 pole E-Trip
V-EA-E Trip
0.3A Through 10A Rated Current
1.05-1.35xIN
Rated
Current
0.3A
0.5A
0.75A
0.8A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
Type/
Cat. No.
3E03UM
3E05UM
3E075UM
NA
Approvals
UL508 Listed
60
40
E137938
10
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
4
1
3E1UM
3E1.6UM
3E2UM
Standard Pack: 6
Weight:
10
4
0.3A - 32A
3E2.5UM
3E3UM
1.8kg (3.97 lb.)
40A - 63A
1
0.4
3E3.5UM
3E4UM
3E5UM
1.98kg (4.37 lb.)
10-1
4x10-2
Three Pole
3E6UM
3E8UM
10-2
4x10-3
3E10UM
3E12UM
3E13UM
3E15UM
3E16UM
3E20UM
3E25UM
3E30UM
3E32UM
3E40UM
3E50UM
3E60UM
3E63UM
10-3
12A
13A
1
2
3
4
5
6
8 10 141820
40
100
Multiple of Rated Current
E0.3A-E10A
15A
16A
35 mm
20A
25A
(1.38 in.)
93.3 mm
(3.67 in.)
30A
32A
V-EA-E Trip
12A Through 60A Rated Current
1.05-1.35xIN
60
40
40A
50A
74.7 mm
(2.94 in.)
52.5 mm
(2.07 in.)
10
60A
63A
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
4
1
10
4
Voltage Rating
480Y/277VAC
0.3-25A: 1 pole - 42VDC; 2 Pole - 80VDC
30-60A: 1 pole - 24VDC; 2 Pole - 60VDC
1
0.4
Short Circuit Withstand Rating
(UL/CSA - Ratings)
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
10-1
4x10-2
Group Short Circuit Withstand Rating
(UL/CSA - Ratings)
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
10-2
4x10-3
Interrupting Capacity (VDE - Ratings)
Calibration Temperature
Operating Temperature
Storage Temperature
0.3-63A (RC): 10kA
10-3
40°C (104°F)
1
2
3
4
5
6
8 10 14 18 20
40
100
Multiple of Rated Current
-25°C to 55°C (-13°F to 131°F)
-40°C to 70°C (-40°F to 158°F)
Terminal Size Acceptability
Terminal Torque
Top: 18-3 AWG; Bottom: 18-2 AWG (Line/Load reversible)
20 lb.in.
IP20
Standard Dual
Connection Terminal
All parts are ring tongue compatible.
Terminal Protection Degree
short circuit Withstand ratings for v-ea manual motor controller
Backup
Protection
UL-Listed
RK5-Fuse
up to 10kA
UL-Listed
MCCB
up to 10kA
No BCP
Required
up to:
Trip
Curve
Ring
tongue
Amp Range
0.3 - 10A
all
all
all
all
4xRC*
min 15A, max 70A
4xRC*
min 15A, max 70A
10kA
5kA
5kA
5kA
Box
clamp
12 - 30/32A
40 - 50A
4xRC*
max 125A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 200A
60 / 63A
4xRC*
max 250A
4xRC*
max 250A
*up to nearest rated current