5秒后页面跳转
3200-3A PDF预览

3200-3A

更新时间: 2024-09-26 00:53:03
品牌 Logo 应用领域
ETAL /
页数 文件大小 规格书
4页 210K
描述
Control equipment, extra-low voltage wiring systems and components

3200-3A 数据手册

 浏览型号3200-3A的Datasheet PDF文件第2页浏览型号3200-3A的Datasheet PDF文件第3页浏览型号3200-3A的Datasheet PDF文件第4页 
Thermal-Magnetic Overcurrent Circuit Breaker 3200  
Description  
Single pole thermal-magnetic circuit breaker with tease-free, trip-free,  
press-to-reset, snap action mechanism and additional manual release  
(M-type TM CBE to EN 60934). Designed for plug-in mounting with E-T-A  
sockets 10 and 16.  
Approved to CBE standard EN 60934 (IEC 60934).  
Typical applications  
Control equipment, extra-low voltage wiring systems and components.  
1
Ordering information  
3200-...  
Type No.  
3200 plug-in  
Current ratings  
0.05...25 A  
Technical data  
For further details please see chapter: Technical Information  
3200 - 5 A  
ordering example  
Voltage rating  
Current ratings  
Typical life  
AC 240 V, 50/60 Hz; DC 28 V  
0.05...25 A  
Standard current ratings and typical internal resistances  
500 operations at 1 x IN, inductive  
4,000 operations at 1 x IN, resistive  
Ambient temperature  
-30...+60 °C (-22...+140 °F)  
Current  
Internal  
Current  
Internal  
Insulation co-ordination  
(IEC 60664 and 60664 A) withstand voltage  
2.5 kV  
rated impulse  
pollution  
degree  
2
rating (A)  
resistance (Ω) rating (A)  
resistance (Ω)  
0.05  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.8  
1
534  
149  
56  
4
0.141  
0.107  
0.060  
0.049  
< 0.02  
< 0.02  
< 0.02  
< 0.02  
< 0.02  
< 0.02  
< 0.02  
< 0.02  
< 0.02  
reinforced insulation in operating area  
5
Dielectric strength  
(IEC 60664 and 60664A) test voltage  
operating area  
6
AC 3,000 V double insulation  
24.2  
13.6  
8.1  
7
Insulation resistance  
Interrupting capacity Icn  
> 100 MΩ (DC 500 V)  
8
0.05...0.8 A  
1...2 A  
2.5...25 A  
self-limiting  
200 A  
400 A  
10  
12  
14  
15  
16  
18  
20  
25  
5.25  
3.55  
2.02  
0.90  
0.51  
0.36  
0.23  
Degree of protection  
(IEC 60529/DIN 40050)  
operating area IP40  
terminal area IP00  
Vibration  
5 g (57-500 Hz), 0.38 mm (10-57 Hz)  
to IEC 60068-2-6, test Fc  
10 frequency cycles/axis  
1.5  
2
Shock  
25 g (11 ms)  
to IEC 60068-2-27, test Ea  
2.5  
3
Corrosion  
Humidity  
Mass  
96 hours at 5 % salt mist  
to IEC 60068-2-11, test Ka  
240 hours at 95 % RH  
to IEC 60068-2-78, test Cab  
approx. 50 g  
Approvals  
Authority Standard  
Rated voltage  
Current ratings  
VDE  
IEC/EN 60934 AC 240 V  
0.05...25 A  
0.05...25 A  
DC 28 V  
1646  
www.e-t-a.de  
1

与3200-3A相关器件

型号 品牌 获取价格 描述 数据表
3200409 PHOENIX

获取价格

Terminal Block Accessory
3200412 PHOENIX

获取价格

Terminal Block Accessory, Ferrule, Copper Alloy,
320042 AMPHENOL

获取价格

Circular Connector
3200438 PHOENIX

获取价格

Terminal Block Accessory, Ferrule, Copper Alloy
3200441 PHOENIX

获取价格

Terminal Block Accessory
320-0500-01 ETC

获取价格

STECKER CINCH HIGH END VERGOLDET ROT
3200506 PHOENIX

获取价格

Terminal Block Accessory, Ferrule, Copper Alloy,
3-2005159-1 TE

获取价格

THIS DRAWING IS A CONTROLLED DOCUMENT.
3-2005159-2 TE

获取价格

THIS DRAWING IS A CONTROLLED DOCUMENT.
3-2005159-3 TE

获取价格

THIS DRAWING IS A CONTROLLED DOCUMENT.