Product: 29532C
VFD, 3C #4/0 Str BC XLPO Ins + #3 Symm. Seg. Gnd (3 of #8) Str BC, CTS,
Blk PVC Jkt, 600V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B
Product Description
Belden Basics VFD, 3 Conductor 4/0AWG (19x10) Bare Copper XLPO Insulation M4 Color Code + 3AWG Symmetrical Segmented Ground (3 of 8AWG) Bare
Copper Stranded, Overall Dual Copper Tapes Helically Applied Shield, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B SUN
RES DIR BUR Oil Resistant
Technical Specifications
Product Overview
Suitable Applications:
AC Motor drives, VFD, Variable Frequency drives
Physical Characteristics (Overall)
Conductor
Element
AWG Stranding
Material
No. of Conductors
4/0
8
19x10
7x16
BC - Bare Copper
BC - Bare Copper
3
3
Ground Wire
Conductor Count:
3
Insulation
Material
Nominal Wall Thickness
XLPE - Cross Linked Polyethylene 0.0575 in
Color Chart
Number
Color
1
2
3
Black and Numbered 1
Black and Numbered 2
Black and Numbered 3
Outer Shield Material
Type Description Layer
Material
Coverage [%]
Tape .002"
Tape .002"
1
2
Spiral Copper 100 %
Spiral Copper 100 %
Outer Jacket Material
Material
Nominal Diameter Nominal Wall Thickness
PVC - Polyvinyl Chloride 1.536 in
Electrical Characteristics
Conductor DCR
0.083 in
Nominal Conductor DCR
0.05 Ohm/1000ft
Capacitance
Nom. Capacitance Conductor to
Conductor
Nom. Capacitance Conductor to Other Conductor to Shield
50 pF/ft