INSTALLATION INSTRUCTIONS  
Ref: IWYSNC – Rev 6 – Sept 02  
Analogue Instruments  
DIN Instruments 240 Series & ANSI  
Switchboard Meters 070 Series  
LED Synchroscope & Synchrocheck  
Relay with Dead Bus  
Setting Up and Maintenance  
The Operation as Synchro Check Relay with Dead Bus  
Units are adjusted before despatch and therefore no  
adjustments are required. Unless a fault develops, the unit  
requires little attention. During routine servicing and  
inspection of the associated equipment, the unit should be  
inspected to normal standards for this class of equipment.  
For example remove accumulations of dust and check all  
connections for tightness and corrosion. In the event of a  
repair being necessary, it is recommended that the unit be  
returned to the factory or to the nearest Crompton  
Instruments Service Centre, (details on page 2). Should  
repair be attempted then replacement components must be  
of the same type, rating and tolerance as those used in the  
original circuit. It is important that should calibration be  
deemed necessary, say after repair, then this should only be  
attempted if the required high accuracy equipment is  
available. With any enquiry please quote the full model  
number found on the side of the label. The unit must be  
recalibrated after repair.  
Relay Ratings  
Single pole changeover 250V, 5A a.c. resistive.  
Model 077-14A 360° LED Synchroscope & 360 LED  
Synchroscope and Synchro Check Relay Models 077-  
14L/D/G/H  
The operation as a Synchroscope  
The 244-14A and 077-14A synchrocopes provide illuminated  
indication of the actual phase difference between the  
generator GEN voltages and the busbar voltage. If the LED  
display rotates clockwise the generator frequency is too high  
and must be reduced and visa versa if the LED display turns  
anticlockwise.  
The 244-14D/H and 077-14D operate in the same way as  
the 244-14L and 077-14L Synchro check relays with the  
addition of a dead bus option. This optional feature enables  
the relay to energise with a GEN supply only thus allowing  
the generator to power the BUS during a supply failure.  
The operation as synchrocheck relay  
The 244-14L/G and 077-14L synchroscopes are based on a  
microcontroller, which interprets the input signals and  
displays the phase and voltage information on a series of  
light emitting diodes (LED’s).  
Connection Diagrams  
Model 244-14A 360° LED Synchroscope & Models 244-  
‘GEN’  
‘BUS’  
L1 L2 L3  
LED Synchroscope and Syn
Twenty four red LED’s are arranged in a ring simulating the  
traditional 360° analogue movement. Only one LED is lit at  
any one time indicating the phase difference between the  
busbar (BUS) and generator (GEN) signals. The unit will  
operate correctly at any frequency within its range.  
The voltage levels of the two input signals are continuously  
measured and compared with the user adjustable voltage  
difference setting. If the measured difference is outside the  
allowable range, the ring of LED’s will be extinguished and  
the red GEN LED will be lit. If the voltage difference is within  
range the green GEN LED will be lit and the ring of LED’s  
will indicate the phase relationship.  
Once the BUS and GEN signals become coincident, the unit  
will wait for an adjustable time delay before lighting the  
green triangular SYNCHRONISED LEDS and operating the  
relay. The ring of LED is also extinguished which means the  
user will only see green LED’s when the generator GEN is  
synchronised with the BUS.  
L2  
L3  
L1relay  
NC  
12  
3
2
6
Relay  
1
C
10  
NO  
5
IN  
NC = Normally closed  
CO = Common  
NO = Normally open  
L O A D  
L O A D  
Terminals 3, 10 and 12 are not  
used on Model 077-14A.  
NC = Normally closed  
CO = Common  
NO = Normally open  
The rear pot adjustments should be set to suit operational  
requirements.  
Terminals 1,3 & 4 are not used  
on Model 244-14A.  
The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and is intended to describe the  
correct method of installation for this product. However, Tyco Electronics has no control over the field conditions, which influence product installation.  
It is the user's responsibility to determine the suitability of the installation method in the user's field conditions. Tyco Electronics' only obligations are those in Tyco  
Electronics' standard Conditions of Sale for this product and in no case will Tyco Electronics be liable for any other incidental, indirect or consequential damages  
arising from the use or misuse of the products. Crompton is a trademark.  
Tyco Electronics UK Limited  
Crompton Instruments  
Freebournes Road, Witham, Essex, CM8 3AH, UK  
Phone: +44 1376 509 509 Fax: +44 1376 509 511  
http://energy.tycoelectronics.com  

与246-076相关器件

型号 品牌 描述 获取价格 数据表
246-07A MACOM 240 Series DIN Panel Meters

获取价格

246-07V MACOM 240 Series DIN Panel Meters

获取价格

2460A ALLEGRO ELECTRONIC IGNITION TIMING

获取价格

2460C ALLEGRO ELECTRONIC IGNITION TIMING

获取价格

2460-EC TEKTRONIX 2460-EC Graphical Potentiostats

获取价格

2460LW ALLEGRO ELECTRONIC IGNITION TIMING

获取价格