Thermal Overcurrent Circuit Breaker 1110-...
Description
Tease-free, trip-free, snap action mechanism. Designed for snap-in
panel mounting utilising round hole or industry standard fuse-holder
cut-out dimensions. Featuring an ergonomically styled two colour
actuator with indicator band clearly showing the tripped/OFF position.
Approved to CBE standard EN 60934 (IEC 60934): S-type TO CBE
Typical applications
Motors, transformers, solenoids, extra low voltage systems, household
and office machines, instrumentation, marine applications, mobile homes.
1
1110-F1..
Ordering information
Type No.
Technical data
1110
snap in panel mounting
Mounting
F1 panel thickness 0.8...1.6 mm (.031 -.063 in)
F2 panel thickness 1.8...3 mm (.071-.118 in)
Number of poles
For further details please see chapter: Technical Information
Voltage rating
Current rating
AC 250 V; DC 50 V
0.05...16 A
1 1-pole protected
Actuator style
Typical life
IN
2
black push button/white indicator ring,
push-push function
operations
Un
I
0.05...10 A
0.05...10 A
0.05...10 A
12...16 A
10,000
10,000
6,000
AC 250 V
DC 28 V
DC 50 V
DC 50 V
1xIN
1xIN
1xIN
1xIN
Terminal design
P1 blade terminals A6.3-0.8 (QC .250)
Characteristic curve
M1 medium delay
2,000
Current ratings
0.05...16A
Ambient temperature
Insulation co-ordination
(IEC 60664 and 60664 A) withstand voltage
2.5 kV
-20...+60 °C (-4...+140 °F)
rated impulse pollution
1110 - F1 1 2 - P1 M1 - 0.05 A = ordering example
degree
2
reinforced insulation in operating area
Preferred types
Dielectric strength
(IEC 60664 and 60664A) test voltage
Preferred types
Standard current ratings (A)
operating area
AC 3,000 V
1 1.5 2 3 3.5 4
5
x
6
x
7
x
8
x
10 15 16
Insulation resistance
Interrupting capacity Icn
> 100 MΩ (DC 500 V)
x
x
x
x
x
x
x
x
x
1110-F112-P1M1-
1110-F212-P1M1-
AC 250 V: 0,05...10 A 8 x IN
DC 50 V:
0,05...6.5 A 10 x IN
x
x
x
x
x
x
x
x
x
7...16 A
7...10 A
130 A
200 A
DC 28 V:
IN
Standard current ratings and typical internal resistance values
Interrupting capacity
UN
(UL 1077/EN60934 PC 1) 0.05...6 A
7...16 A
AC 250 V
AC 125 V
1,000 A
1,000 A
1,000 A
Current
rating (A)
Internal
Current
Internal
resistance (Ω)
0.05...16 A DC 50 V
resistance (Ω) rating (A)
Degree of protection
(IEC 60529/DIN 40050)
operating area IP40
terminal area IP00
0.05
0.08
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1
442
173
110
27.8
12.4
7.0
2
0.25
Vibration
8 g (57-500 Hz) 0.61 mm (10-57 Hz),
to IEC 60068-2-6, test Fc,
10 frequency cycles/axis
2.5
3
0.19
0.12
Shock
30 g (11 ms)
to IEC 60068-2-27, test Ea
3.5
4
0.09
0.07
Corrosion
Humidity
Mass
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
5
0.05
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
4.5
6
0.04
approx. 12 g
3.1
7
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
2.3
8
Approvals
1.7
10
12
15
16
Authority
Standard
Rated voltage
Current ratings
1.1
AC 250 V
DC 50 V
0.05 A…10 A
0.05 A…16 A
VDE
IEC/EN 60934
1.2
1.5
1.8
0.71
0.41
0.38
AC 250 V
AC 120 V
DC 50 V
0.05 A…6.6 A
7 A…16 A
0.05 A…16 A
UL
UL 1077
C22.2 No 235
AC 250 V
DC 50 V
0.05 A…16 A
0.05 A…16 A
CSA
C22.2 No 235
1646
www.e-t-a.de
1