Midget Fuses
Supplementary Overcurrent Protection
Ampere Ratings:
BLN Fuses
FAST-ACTING 250 VAC
1
2
3
4
5
6
8
10
12
15
20
25
30
ꢀ
Fiber tube, 250 volt BLN fuses provide low-
cost protection for military applications and
control circuits.
Approvals: UL Listed per UL 248 (formerly
198G) (File No. E10480). CSA Certified to
Spec 59.2 (File No. LR29862). Versions
available to meet MIL Spec MIL-F-15160/9,
QPL F09A: Contact factory.
Voltage Rating: 250 Volts AC
Interrupting Rating: 10,000 amperes rms
symmetrical
Dimensions: 13/32" x 1-1/2"
MIDGET &
ELECTRONIC
FUSES
Example part number (series & amperage): BLN 30
Ampere Ratings:
BLF Fuses
FAST-ACTING 125/250 VAC
1
⁄
2
3
4
5
6
7
8
9
10
12
15
20
25
30
ꢀ
1
11⁄
2
2
Laminated tube BLF fuses are the lowest
price midget fuse. They are suitable for
control circuit and instrument protection in
dry locations.
21⁄
2
61⁄
4
Approvals: UL Listed per UL 248 (formerly
198G) (File No. E10480). CSA Certified to
Spec 59.2 (File No. LR29862).
Voltage Ratings: 250 Volts AC: 1/2 – 15
amperes; 125 Volts AC: 20 – 30 amperes
Interrupting Rating: 10,000 amperes rms
symmetrical
Dimensions: 13/32" x 1-1/2"
Example part number (series & amperage): BLF 5
Ampere Ratings:
BLS Fuses
FAST-ACTING 250/600 VAC
2
⁄
10
10
1
2
3
4
5
6
7
8
10
ꢀ
4
⁄
11⁄
2
1
16⁄10
18⁄10
BLS fuses are 1-3/8" long in contrast to
other midget fuses which are 1-1/2". They
provide space-saving, low-cost, protection
to street lighting, metering, control and
electronic circuits.
⁄
2
3
⁄
4
8
⁄
10
Approvals: UL Listed per UL 248 (formerly
198G) (File No. E10480): 1/2 – 5 amps.
CSA Certified to Spec 59.2 (File No.
LR29862): 1/2 – 5 amps.
Voltage Rating: 600 Volts AC: 2/10 – 5
amperes; 250 Volts AC: 6 – 10 amperes
Interrupting Rating: 10,000 amperes rms
symmetrical
Dimensions: 13/32" x 1-3/8"
Example part number (series & amperage): BLS 10
Ampere Ratings:
FLA Fuses
TIME-DELAY 125 VAC
⁄
10
11⁄
11⁄
8
28⁄10
3
61⁄
7
8
10
12
15
20
25
30
4
1
ꢀ
15
⁄100
4
2
⁄
10
14⁄10
32⁄10
FLA fuses are 125 volt, pin-indicating time-
delay fuses for protection of control circuit
transformers, solenoids, and other circuits
with high inrush currents. Metal indicating pin
“pops-out” when fuse opens. Pin gives visual
indication of open fuse. Use FLA fuses in
conjunction with special fuseblocks to operate
mechanical signal switches or energize alarm
circuits. Fuses rated 12 amperes and above
have dual-tube construction.
1
⁄
4
11⁄
2
31⁄
2
3
4
1
6
8
⁄
10
16⁄10
18⁄10
2
4
*
*
*
*
*
⁄
10
41⁄
5
2
⁄
2
⁄
⁄
10
21⁄
4
56⁄10
6
10
21⁄
2
1
Approvals: UL Listed per UL 248 (formerly
198G) (File No. E10480). CSA Certification
pending.
Voltage Rating: 125 Volts AC
Dimensions: 13/32" x 1-1/2"
Interrupting Rating: 10,000 amperes rms
symmetrical
Note: Dual tube construction
Example part number (series & amperage): FLA 15
*
RECOMMENDED FUSE BLOCKS
L60030M series. Refer to Fuse Block section of this catalog for additional information.
49