UT 6-TMC M...
2
Ordering data
Circuit breakers
Description
Nominal current Type
Order No.
0916603
0916604
0916605
0916606
0916607
0916608
0916609
0916610
0916611
0916612
0916613
Pcs./Pkt.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
0.5 A
1 A
UT 6-TMC M 0,5A
6
6
6
6
6
6
6
6
6
6
6
UT 6-TMC M 1A
UT 6-TMC M 2A
UT 6-TMC M 4A
UT 6-TMC M 5A
UT 6-TMC M 6A
UT 6-TMC M 8A
UT 6-TMC M 10A
UT 6-TMC M 12A
UT 6-TMC M 15A
UT 6-TMC M 16A
2 A
4 A
5 A
6 A
8 A
10 A
12 A
15 A
16 A
Accessories
Description
Type
Order No.
3030336
3030242
3030255
3030349
3030271
3030365
3047345
1205066
Pcs./Pkt.
Plug-in bridge, for cross connection in the bridge shaft, red, 2-pos.
Plug-in bridge, for cross connection in the bridge shaft, red, 3-pos.
Plug-in bridge, for cross connection in the bridge shaft, red, 4-pos.
Plug-in bridge, for cross connection in the bridge shaft, red, 5-pos.
Plug-in bridge, for cross connection in the bridge shaft, red, 10-pos.
Plug-in bridge, for cross connection in the bridge shaft, red, 20-pos.
Warning label, for UT series, yellow
Screwdriver
UniCard sheet, for labeling
Zack marker strip, for labeling
FBS 2-6
FBS 3-6
FBS 4-6
FBS 5-6
FBS 10-6
FBS 20-6
WS UT 6
SZS 1,0X4,0
UC-TM 12
ZB 12
50
50
50
50
10
10
10
10
(See CLIPLINE catalog)
(See CLIPLINE catalog)
3
Electrical data
Nominal current, nominal voltage, and additional electrical data
Rated insulation voltage
Rated frequency
Nominal voltage
440 V AC
50/60 Hz (at 240 V AC)
240 V AC, 28 V DC
Nominal current AC/DC
Operating voltage range
Operating frequency range
Insulation resistance (main circuit)
Insulation resistance
Depending on module: 0.5 A, 1 A, 2 A, 4 A, 5 A, 6 A, 8 A, 10 A, 12 A, 15 A, 16 A
50 V AC ... 264 V AC, 5 V DC ... 30.8 V DC
48 Hz ... 62 Hz
> 100 MΩ
50 Hz: 2000 V
Pulse: 2800 V
II
Surge voltage category
Pollution degree
2
AC
DC
Switching cycles
Service life under load
6000 cycles at 1 x I
6000 cycles at 1 x I
n
n
Overload according to IEC 60943
Overload according to UL 1077
Short-circuit switching capacity (Inc)
Conditional short-circuit switching capacity (Inc)[Backup fuse]
40 cycles at 6 x I
50 cycles at 1.5 x I
200 A
40 cycles at 6 x I
n
n
50 cycles at 1.5 x I
400 A
n
n
2000 A
2000 A
103943_en_04
PHOENIX CONTACT
2