Effect on thermal tripping of mounting in rows
Calculation example for overdimensioning
5 circuit breakers with In = 10 A are to be mounted in rows.
The ambient temperature is +23°C.
Nominal current when not mounted In = 10 A
in rows
NOTE: When mounted in rows with simultaneous
load, a mutual thermal effect occurs.
The mutual thermal effect is tantamount to an increase in the
ambient temperature (see page 5). This depends on the
following:
Typical correction factor
df = 1.25
Theoretical nominal current when
mounting in rows
In row = 10 A X 1.25
= 12.5 A
–
–
–
–
The nominal current
The ambient temperature
The number of devices
The distance between devices
3.3
Internal resistance of the UT 6-TMC M
Nominal current
0.5 A
Resistance
4.37 Ω
The nominal device current can be either overdimensioned
or limited. When the UT 6-TMC M is mounted in rows, the
correction factor is usually in the range of 1.25 or at
80% (reciprocal) in relation to the limiting nominal current.
These values apply in the event of continuous load and at an
ambient temperature of +23°C.
Since the thermal effect varies for each planned installation
when mounting in rows, the correction factors must be
defined individually and tested.
1.0 A
0.95 Ω
2.0 A
0.33 Ω
4.0 A
5.0 A
6.0 A
8.0 A
10.0 A
12.0 A
15.0 A
16.0 A
88.0 mΩ
55.8 mΩ
41.7 mΩ
22.2 mΩ
12.3 mΩ
10.9 mΩ
8.3 mΩ
7.7 mΩ
Measurement between the LINE and LOAD connections.
Tolerance: ±10%
4
Mechanical data
Fixing
Mounting method
On a DIN rail according to DIN EN 60715, NS 35N/7,5 or NS 35/15
The tripping characteristics are not dependent on the mounting position.
Plug-in bridge, for cross connection in the bridge shaft
FBS x-6 plug-in bridge (see "Accessories" on page 2)
Connection polarity
Suitability
Weight
Independent polarity (for DC) for the LINE and LOAD connections
"Factory wiring"
51 g
Housing material
Fuse type
PA 66
Medium blow fuse
Inflammability class according to UL 94
Maximum number of cycles
V0
6000 at 1 x I
n
Connection terminal block
Screw connection
M4
Connection capacity
1 conductor
2 conductors (two conductors with same cross-section, ferrule without
plastic sleeve)
Solid
0.2 mm² ... 10 mm²
Stranded
0.2 mm² ... 10 mm²
0.2 mm² ... 2.5 mm²
With ferrule
0.25 mm² ... 6 mm²
0.25 mm² ... 1.5 mm²
2 stranded conductors with a TWIN ferrule
Stripping length
0.5 mm² ... 4 mm²
12 mm
Tightening torque (EN 60934)
1.5 Nm ... 1.8 Nm