Thermal Magnetic Circuit Breakers - UL 1077
TMC 60 Series for mounting on 35 mm DIN rail
Overview
Standard current ratings and typical internal resistance values
TheTMC 60 Series provides supplemental overload and short-circuit protection.
An interrupt capacity of 10 kAIC at 480 / 277V AC and DC ratings make the series
ideal for a wide range of applications.
One-pole
Two-pole
Three-pole
Part Number
0902014
0902027
0902030
0902043
0902056
0902069
0902072
0902085
0902098
0902108
0902111
0902124
0902137
0902140
0902153
Description
TMC 61C 0,5A
TMC 61C 01A
TMC 61C 02A
TMC 61C 03A
TMC 61C 04A
TMC 61C 06A
TMC 61C 10A
TMC 61C 13A
TMC 61C 16A
TMC 61C 20A
TMC 61C 25A
TMC 61C 32A
TMC 61C 40A
TMC 61C 50A
TMC 61C 63A
Part Number
0902166
0902179
0902182
0902195
0902205
0902218
0902221
0902234
0902247
0902250
0902263
0902276
0902289
0902292
0902302
Description
Part Number
0902315
0902328
0902331
0902344
0902357
0902360
0902373
0902386
0902399
0902409
0902412
0902425
0902438
0902441
0902454
Description
TMC 63C 0,5A
TMC 63C 01A
TMC 63C 02A
TMC 63C 03A
TMC 63C 04A
TMC 63C 06A
TMC 63C 10A
TMC 63C 13A
TMC 63C 16A
TMC 63C 20A
TMC 63C 25A
TMC 63C 32A
TMC 63C 40A
TMC 63C 50A
TMC 63C 63A
TMC 62C 0,5A
TMC 62C 01A
TMC 62C 02A
TMC 62C 03A
TMC 62C 04A
TMC 62C 06A
TMC 62C 10A
TMC 62C 13A
TMC 62C 16A
TMC 62C 20A
TMC 62C 25A
TMC 62C 32A
TMC 62C 40A
TMC 62C 50A
TMC 62C 63A
These DIN rail-mountable circuit breakers are available in one-, two- and three-pole
configurations. An auxiliary contact in S- or H-function status output is also available.
TheTMC 60 Series is UL recognized, CSA approved and carries the CE mark.
Typical Application
Circuit protection for power supplies, UPS, controller I/O points, relay/contactor
coils, control circuits, appliances and motor circuits.
Technical Data
Vibration
3 g (10 to 55 Hz) to IEC 68-2-6
C: 0.5-63A
MaximumVoltage Rating
Interrupting Capacity
Current Rating Range
AC 277 / 480V
10,000 Amps
Trip Characteristics
Torque
4.5 Nm / 39.8 lbf-in
0.05 A to 63 A
Vibration
(per IEC 60077)
Temperature Range
OperatingTemperature
StorageTemperature
3 g (in x, y, z direction)
-25° to +55°C (-13° to +131°F)
-55° to +55°C (-67° to +131°F)
Plastics Rating per UL 94 V0
Typical time/current characteristics at 23 degrees Celsius
InsulationValues
(IEC 664 and 664A)
Operating Area
Protection Level
IP 20
Rated ImpulseWithstandVoltage Pollution Degree
10,000
1,000
100
10
10,000
1,000
100
10
10,000
1,000
100
10
Configuration
Weight
1 pole
125 g
2 pole
250 g
3 pole
375 g
Direct Current -
6.0 k V
3
lower trip limit 1,01 lN
upper trip limit 1,45 lN
rated current up to AC 6A
lower trip limit 1,01 lN
upper trip limit 1,45 lN
rated current AC 10-40A
(50A 1-pole)
lower trip limit 1,01 lN
upper trip limit 1,45 lN
rated current AC 63A
Magnetic tripping currents are
increased by 30 percent in DC
circuits with the effect of shifting
the magnetic trip range 30 percent
to the right of Alternating Current
(AC) trip curves.
Insulation Resistance
>100 MΩ (DC 500V)
(50A 2+3 pol.)
Life at Rated
Current Mechanical
6,000 operations (UL tested)
10,000 operations
Cable Size
max 35 mm2 / AWG 2 (LINE)
max 25 mm2 / AWG 3 (LOAD)
max 2.5 mm2 / AWG 12 (auxiliary circuits)
Minimum 1 mm2 or AWG 16 for all circuits. Use a ferrule with wire sizes smaller than 16 AWG.
1
1
1
0.1
0.1
0.1
0.01
0.01
0.01
0.001
0.001
0.001
0.8 1
0.8 1
2
3
4
6
8 10
20 30 50 70 100
0.8 1
2
3
4
6
8 10
20 30 50 70 100
2
3
4
6
8 10
20 30 50 70 100
. . . times rated current
. . . times rated current
. . . times rated current
(multipole types: all poles symmetrically loaded)
Amps
Temperature
-20˚C -15˚ -10˚ -5˚
The time/current characteristic curve depends on the ambient
0˚ +5˚ +10˚ +15˚ +20˚ +25˚ +30˚ +35˚ +40˚ +45˚ +50˚
temperature prevailing. In order to eliminate nuisance tripping, multiply
the circuit breaker current ratings by the derating factor shown at right.
-4˚F +5˚ +14˚ +23˚ +32˚ +41˚ +50˚ +59˚ +68˚ +77˚ +86˚ +95˚ +104˚+113˚+122˚
0.84 0.85 0.87 0.88 0.89 0.91 0.93 0.94 0.96 0.98 1.00 1.02 1.04 1.06 1.09
0.75 0.77 0.78 0.81 0.83 0.85 0.88 0.90 0.93 0.96 1.00 1.04 1.09 1.14 1.20
0.79 0.80 0.82 0.84 0.86 0.88 0.90 0.93 0.94 0.97 1.00 1.03 1.06 1.11 1.15
0.81 0.83 0.84 0.85 0.87 0.89 0.91 0.93 0.94 0.97 1.00 1.02 1.05 1.09 1.12
0.5 - 4.0
8.0 - 10
13 - 40
50-60
8
9