Ground Fault Relays
Function:
WILMAR™ Protective Relays – WC1G Series - Grounded
WILMAR Ground Fault Detectors are designed to pro-
vide very sensitive Ground-Current protection for mo-
tor, equipment and personnel from damage or electrical
shock. In a ground system, the leakage current is moni-
tored through a toroidal or doughnut current transformer
placed around the supply conductors to a motor, trans-
former, equipment or outlets. Since the sums of the
current in a system add to zero, the relay is responsive
only to ground-fault current.
TERMINAL STRIPS
#6 - 32 SCREWS
Operation:
3.8
The output contacts are shown in de-engerized
position. They will change state when these condi-
tions are met:
3.0
1. Control voltage is applied.
2. Leakage current exceed the trip setting.
17
/
64" DIA.
4 MTG. HOLES
Note: Dimensions in inches.Multiply by values by 25.4 for dimensions in mm.
Current Transformer
PRODUCT SPECIFICATIONS
PART NUMBER SELECTION
Part Number
WC1G Series
Sample Part No.
Model:
WC1G-120AC
CT Window Diameter .......................
Leakage Current Range ...................
Control Voltage ................................
Output Contacts ...............................
Operating Temperature ....................
Contact Ratings ................................
1.7 inches (std) or can be specified by customer
10 to 60 mA
WCIG-
Control Voltage
120AC
See Part Number Selection
220AC
One set N.C., one set N.O.
230AC
40oC to +65oC
380AC
400AC
10 amp resistive at 250 Vac, 8 amp. resistive @ 30 Vdc
460AC
480AC
Notes:
575AC
1. Remove screw for acess to the pick-up adjustment potentiometer.
2. Clockwise rotation of the adjustment potentiometer will raise the relay sensitivity.
4 5
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)